Data Aire’s dap4 Modbus TCP/IP 

 

Document:

 

600

000

961

 

version

 

4.0

 

7

 

 

Point

 

Index

 

Description

 

Read/

Write

 

Variable

 

Name

 

Data

 

Type

 

Modbus

 

TCP/IP

 

32 

Temperature deadband for heating in economizer mode* 

R/W 

Econ_Ht_Deadband 

40033 

33 

Amount temp must change for each stage of heat/cool* 

R/W 

Stage_sp 

40034 

34 

Dewpoint setpoint for economizer* 

R/W 

Dewpoint_Hi_SP 

40035 

35 

deadband of dewpoint for economizer* 

Dewpoint_Hi_Dband 

30036 

36 

Lower limit of dewpoint for economizer* 

R/W 

Dewpoint_Lo_SP 

40037 

37 

deadband of low dewpoint for economizer* 

Dewpoint_Lo_Dband 

30038 

38 

deadband of enthalpy for economizer* 

Enthalpy_Deadband 

30039 

39 

Offset for Outside Air Temperature probe* 

R/W 

Ain_offs 

40040 

40 

Temperature of the outside air* 

Outside_Temp 

30041 

41 

Dew point of outside air* 

Outside_Dewpt 

30042 

42 

Dew point of return air* 

Ret_Air_Dewpt 

30043 

43 

Setpoint for fan modulation by return or rack temperature* 

R/W 

RA_Fan_Setpoint 

40044 

44 

Amount from setpoint before fan starts ramping up* 

R/W 

RA_Fan_Deadband 

40045 

45 

The highest of the rack temp sensors connected to this unit* 

Rack_Temp 

30046 

46 

The highest rack temp of all units in this zone* 

Zone_Rack_Temp 

30047 

47 

Value of rack temperature sensor #1* 

Rack_T1 

30048 

48 

Value of rack temperature sensor #2* 

Rack_T2 

30049 

49 

Value of rack temperature sensor #3* 

Rack_T3 

30050 

50 

Temperature setpoint of the Zone Master* 

Master_Temp_Setpoint 

30051 

Lower limit alarm of discharge air temp* 

R/W 

Disch_Air_Lo_SP 

45002 

Relative humidity displayed as xx% 

Humidity_dis 

35003 

Cooling Stages On = Cooling stages are currently on – This point applies to 
DX unit only 

Stages_On 

35004 

Number of heat stages running 

Heaters_On 

35005 

Maximum humidity in last 24hrs 

Maximum 

35006 

Minimum humidity in last 24hrs 

Minumum 

35007 

Cooling Utilization Over Last Hour -Percentage of cooling is used in the last 
hour of operation; this point applies to DX unit. 

Comp_duty 

35008 

Heating Utilization Over Last Hour -Percentage of heating is used in the 
last hour of operation 

Heat_duty 

35009 

Humidifier Utilization Over Last Hour -Percentage of humidifier is used in 
the last hour of operation 

Hum_duty 

35010 

10 

Compressor 1 Runtime -This point applies to DX unit with one compressor 
-high 

R C1_Hours_H 

35011 

11 

Compressor 1 Runtime -This point applies to DX unit with one compressor 
-low 

R C1_Hours_L 

35012 

12 

Compressor 2 Runtime -This point applies to DX unit with dual compressor 
- high 

R C2_Hours_H 

35013 

13 

Compressor 2 Runtime -This point applies to DX unit with dual compressor 
- low 

R C2_Hours_L 

35014 

14 

Heater 1 Runtime - high 

Ht1_Hours_H 

35015 

15 

Heater 1 Runtime - low 

Ht1_Hours_L 

35016 

16 Current 

second 

R  CURRENT_SECOND 

35017 

Содержание dap4 touch

Страница 1: ...Data Aire dap4 Controller MODBUS TCP IP Protocol Integration Instructions Data Aire Inc 230 West BlueRidge Ave Orange CA 92865 Document number 600 000 961 November 2012 Revision 4 0...

Страница 2: ...Data Aire s dap4 Modbus TCP IP Document 600 000 961 version 4 0 2 Table of Content I Modbus TCP IP Setup Procedures for dap4 Ethernet Card page 3 II Modbus TCP IP BMS Points page 6...

Страница 3: ...hold the button on the card Now power on the dap4 controller Wait approximately 20 seconds until the status LED begins to blink red 3 times slowly After the first Red blink release the push button Aft...

Страница 4: ...d you will be taken to the following screen 9 Click the configuration tab on the left Then click on the BACnet tab across the top of the screen 10 This field is where you can change the settings for t...

Страница 5: ...ately 5 minutes for the IP address change to take 18 If there is no communication between the card and the BMS network the Push Button can be used to recall the factory setting configuration of the ca...

Страница 6: ...Sensor Calibration Optional chilled water temperature sensor required B10 R Ain_offs A 30012 12 Temperature setpoint for Energy saver chilled water R W EngSaver_Setpoint A 40013 13 Value of the analog...

Страница 7: ...re sensor 2 R Rack_T2 A 30049 49 Value of rack temperature sensor 3 R Rack_T3 A 30050 50 Temperature setpoint of the Zone Master R Master_Temp_Setpoint A 30051 1 Lower limit alarm of discharge air tem...

Страница 8: ...on optional alarm screen some also add function R Alarm4_txt I 35037 37 Comps 0 none 1 one 2 one UL 3 two 4 two UL 5 Four two circuit R Comp_sel I 35038 38 0 none 1 comp limited 2 twocomp limited 3 co...

Страница 9: ...7 NTC HT 8 50T90 9 10T170 R Ain_type I 35070 70 CW Fan speed controlled by BMS R W CW_Fan_Speed_bms I 45071 71 DX Fan speed controlled by BMS R W DX_Fan_Speed_bms I 45072 72 Maximum Fan speed of outpu...

Страница 10: ...an speed modulation percentage bases on output singal R Fan_Out I 35110 110 Setting of HP alarms hr before comp is locked out 1 disabled R W HP_Lockout_Cnt I 45111 111 Number of HP alarms C1 had withi...

Страница 11: ...Humidity_fail D 10016 16 Sensor is out of range R Ret_Air_fail D 10017 17 Maintenance Schedule Due alarm R Maint_alm D 10018 18 High pressure compressor 1 alarm R C1_HP_alm D 10019 19 Low pressure com...

Страница 12: ...l humidity cycling R Hum_Expect D 10050 51 Units of temperature 0 F 1 C R W USAshr_f_c D 00052 52 Lead compressor select 0 C1 1 C2 R Lead_Comp D 10053 53 Water valve direct or reverse acting R WtrVlv_...

Страница 13: ...fied 13 ONbyZM On by Zone Master Unit Off code 2 OFFbyALR off by alarm that controlled by ZM 3 OFFbyZM manually configured to off by ZM 4 OFFby BMS 5 OFFbySCH off by scheduler 6 STBbyZM send to standb...