30
MENU
- To view Sub-Menu 3-21: FAN SPEED CONTROL FOR CW COOLING
Display will read
3-21 FAN SPEED FOR CW COOLING
SELECT
or
- To view current setting
Display will read
3-21 FAN SPEED CONTROL FOR CW COOLING
FAN SPEED: CONSTANT SPEED
or one of the following
CONSTANT STATIC PRESSURE
PROPORTIONAL TO VALVE
CONTROLLED BY BMS
SELECT
or
- To change current setting.
MENU
- To view Sub-Menu 3-22: MAXIMUM FAN SPEED
Display will read
3-22 MAXIMUM FAN SPEED
SELECT
or
- To view current setting.
Display will read
3-22 MAXIMUM FAN SPEED
FAN SPEED: 100%
Maximum fan speed is adjustable from 70 to 100%.
Factory setting is 100%.
MENU
- To view Sub-Menu 3-23: MINIMUN FAN SPEED
Display will read
3-23 MINIMUM FAN SPEED
SELECT
or
- To view current setting
Display will read
3-23 MINIMUM FAN SPEED
FAN SPEED: 70%
MInimum fan speed is adjustable from 40 to 100%.
Factory setting is 70%.
SELECT
or
- To change current setting.
MENU
- To view Sub-Menu 3-24: DIFFERENTIAL PRESSURE SETPOINT
Display will read
3-24 DIFFERENTIAL PRESSURE SETPOINT