17
PUSH BUTTON FUNCTIONS
The Data Alarm Processor-III panel has seven pressure sensitive feedback-type buttons on the face of the panel. All
programming functions and/or settings are done from the face of the panel. Their functions are as follows:
IMPORTANT NOTE:
The RAM SIGNATURE test often displays “FAIL” on initial start-up because the RAM does not have any stored data.
Simply press “SELECT”
to bypass the “FAIL” message. Once the processor is on-line and operating, the RAM will
collect data and the test should pass on future restarts. On start-up, remember to remove the protective paper on the
battery before turning the unit on. Otherwise, the RAM SIGNATURE will fail on future restarts.
Each time a MENU or SELECT button is pressed, it will advance to the next menu, sub-menu, or selection. If the button
is held down, the menus or selections will advance at a rapid rate. If there is no button activity for three (3) minutes the
panel will return to its normal operating mode.
When a menu fi rst appears, it will have a menu number and title. The fi rst time a SELECT button is pressed, the current
value or option in memory is displayed. Additional pressing of a SELECT button will cause alternate values, options
or selections to be displayed. The SELECT button should be pressed until the desired value, option or selection is
displayed. After the desired value, option or selection has been chosen, the MENU button is pressed to save the last
displayed entry into memory and to advance to the next menu display. The EXIT button can be pressed at any time
to return the panel to its normal operating mode. In this mode, the panel will scroll and display the current system
functions, temperature, humidity and ID number. If an alarm is present it will also be displayed.
ON/OFF
- Soft switch that
turns the power on
or off to the micro-
processor
Menu
- Advances the menus
in ascending order
from 1 to 10
Menu
- Advances the menus
in descending order
from 10 to 1.
Select
-
Selects an option or value in
ascending order.
Select
-
Selects an option or value
in descending order
ALARM SILENCE
Silences the audio alarm
EXIT -
Saves the new settings,
exits the menu function
and returns the panel
to its normal operating
mode