21
NOTE:
If the wrong password is entered, the display will read
WRONG PASSWORD DELAY 60 SECONDS
The message will continue to display for 60 seconds. At the end of 60 seconds the display will return to
CURRENT OPERATING FUNCTIONS & STATUS DISPLAY.
Display will read:
GROUP 1 – STATUS & HISTORY
MENU
- Display will read:
GROUP 2 – SETPOINTS
SELECT
- To see SUB-MENU 2-1: CHANGE TEMPERATURE SETPOINT
Display will read:
2-1 CHANGE TEMPERATURE SETPOINT
SELECT
or
- To display current temperature setpoint
Display will read:
2-1 CHANGE TEMPERATURE SETPOINT
SET AT: nnF
SELECT
or
- To scroll to desired temperature setpoint in 1
º
increments.
(Temperature setpoint is adjustable from 65 to 85º F/18.3 to 29.4º C.
Factory setting is 72º F / 22.2º C)
To save setting and return to Menu Group 2 depress
EXIT
button or
MENU
- To display SUB-MENU 2-2: CHANGE TEMPERATURE DEADBAND
Display will read:
2-2 CHANGE TEMPERATURE DEADBAND
SELECT
or
- To display current temperature deadband.
Display will read:
2-2 CHANGE TEMPERATURE DEADBAND
SET AT: n.nF
SELECT
or
- To scroll to desired setting.
(Temperature deadband is adjustable ± 1 to 5º F/C in 0.1º increments.
Factory setting is 2.0º F. / -16.7º C)
To save setting and return to Menu Group 2 depress
EXIT
button or...
MENU
- To display SUB-MENU 2-3: CHANGE HUMIDITY SETPOINT
Display will read:
2-3 CHANGE HUMIDITY SETPOINT
SELECT
or
- To display current humidity setpoint.
Display will read:
2-3 CHANGE HUMIDITY SETPOINT
SET AT: nn%
SELECT
or
- Scroll to desired setting in 1% increments.
(Humidity setpoint is adjustable from 25 to 70% RH.
Factory setting is 50%.)
MENU
- To display SUB-MENU 2-4: CHANGE HUMIDITY DEADBAND
Display will read:
2-4 – CHANGE HUMIDITY DEADBAND
Group 2
Содержание DAP III