22
SELECT
or
- To display humidity deadband
.
Display will read:
2-4 CHANGE HUMIDITY DEADBAND
SET AT: nn.n%
SELECT
or
- Scroll to desired setting, in 0.1% increments.
(Humidity deadband is adjustable from 1.0 – 15.0% relative humidity.
Factory setting is 3.0%.)
MENU
- To display SUB-MENU 2-5: CHANGE COOLING STAGE-TO-STAGE DB
Display will read:
2-5 CHANGE COOLING STAGE-TO-STAGE DB
SELECT
or
- To view cooling stage-to-stage deadband.
Display will read:
2-5 CHANGE COOLING STAGE-TO-STAGE DB
SET AT: n.nF
SELECT
or
- Scroll to desired setting, in 0.1
º increments.
(Cooling stage-to-stage deadband is adjustable from 0.3 to 3.0ºF / -17.6 to -16.1ºC.
Factory setting is 0.3º F/C.)
MENU
- To display SUB-MENU 2-6:CHANGE E-SAVER CW TEMPERATURE SETPOINT
Display will read:
2-6 – CHANGE E-SAVER CW TEMPERATURE SP
SELECT
or
- To view current E-SAVER CW temperature setpoint.
Display will read:
2-6 – CHANGE E-SAVER CW TEMPERATURE SP
ENERGY SAVER AVAILABLE AT nn
F
SELECT
or
- Scroll to desired setting, in
1
º
increments.
(Energy Saver CW temperature setpoint is adjustable from 40 to 60ºF / 4.4 to 15.6ºC Factory setting is 50ºF/C)
MENU
- To display SUB-MENU 2-7: CHANGE E-SAVER CW TEMPERATURE DEADBAND
Display will read:
2-7 – CHANGE E-SAVER CW TEMPERATURE DB
SELECT
or
- To view E-SAVER CW temperature deadband.
Display will read:
2-7 – CHANGE E-SAVER CW TEMPERATURE DB
SET
AT
n.nF
SELECT
or
- To scroll to desired setting, in
1
º
increments.
(Energy Saver CW temperature deadband is adjustable 1.0 to 5.0ºF/ -17.2 to -15ºC. Factory setting is 1.0ºF/C)
EXIT
- Press EXIT to return to
GROUP 2 - Setpoints
EXIT
- Press EXIT again to return to operational mode.