background image

R

 

www.danvex.fi

 

8

 

 

 

Technical data of AD-400

 

Moisture output 2 kg/hour (at +20

о

C and RH 60%)

 

Table 2

 

Parameter

 

Unit

 

Value

 

Dehumidified air*

 

Rated air consumption

 

 

m

3

/hour

 

 

400

 

Reactivation air*

 

Rated air consumption

 

 

m

3

/hour

 

 

150

 

Electric power and rated current

 

Total power

 

Voltage (1 phase

50 Hz)

 

 

kW 

V

 

 

2.2

 

230

 

Reactivation air heater

 

Heater capacity 
Heater type

 

 

kW

 

-

 

 

1.1

 

РТС

 

Miscellaneous data

 

Maximum sound pressure level 
Operational temperatures range 
Standard filter: dehumidified air 
Reactivation air

 

IEC protection, the whole dehumidifier

 

 

dB(A)

 

о

С

 

-

 

-

 

-

 

 

48

 

–20…+40

 

EU3 

EU3 
IP44

 

The above mentioned values are nominal based on the air temperature of 20

о

С and the air density of 1,2kg/m

3

 

 

Commissioning

 

 

Start up procedures:

 

1. Make sure the dehumidifier is disconnected from the power supply source and that its main 
switch is in OFF position.

 

2. Open the dehumidifier service panels and make sure there are no foreign matters inside 
the dehumidifier.

 

3. Make sure all air throttles are opened and that channels are clean and not blocked.

 

4. Make sure that air filters are installed and clean.

 

5. Manually turn the fans impellers and make sure they rotate freely.

 

6. Check the internal fuse.

 

7. Close the service panels and connect the dehumidifier to 230V power supply.

 

8. For the dehumidifier to operate in manual mode turn the switch to I (MAN) position.

 

9. For the dehumidifier to operate in automatic mode turn the switch to II ( AUTO) position. 
The indication on the controller will light up: upper line – current relative humidity, bottom line

 

- set relative humidity. Using ◄►,

,

▼ 

buttons set the required RH value, when doing so

 

«5d» should be displayed in the upper line, the bottom line should display the value being 
set.Then set the humidity change value (relative to the set value) at which the dehumidifier 
will turn on to maintain the set humidity level (in the upper line of the display «SHС» will be 
displayed, in the bottom line the humidity change value will be displayed (delta).

 

10. To turn the dehumidifier off set the switch to OFF position (middle position).

 

11.  After turning off the dehumidifier fans can continue operation for some time till the 
adsorption rotor cools down to the required temperature.

 

Содержание AD-400

Страница 1: ...DanVex AD 400 Adsorption air dehumidi er Operation manual...

Страница 2: ...R www danvex...

Страница 3: ...NT Safety instructions 3 Introduction 4 Purpose 4 Design 4 Operation principle 5 Dimensions and weight 5 Installation 6 Technical data 7 Commissioning 7 Maintenance 8 Transportation 8 Parts list 9 War...

Страница 4: ......

Страница 5: ...explosion hazard Before opening any panels of the unit body it is required to disconnect the dehumidi er from the mains Before starting any maintenance works the dehumidi er should be out of operatio...

Страница 6: ...all volume of the rotor This material is highly ef cient for water molecules attraction and retention it is noncombustible and explosion proof with a long service life The rotor manufacturing technolo...

Страница 7: ...ondition DRY AIR and is directed to a certain part of the building or a technological process where dehumidi ed air or a certain air humidity levels are required Since the rotor rotates slowly the inc...

Страница 8: ...e rotor The rotor is reactivated by another air ow preheated to 120 C The moisture is removed from the room in the form of moist air Pic 1 Dehumidi er air ows diagram Pic 2 AD 400 dehumidi er dimensio...

Страница 9: ...upright it should be insulated and drain holes should be drilled in the lowest part of the elbow bend 2 4 mm Regeneration airduct The regeneration air duct should be as short as possible A metal net...

Страница 10: ...ls are clean and not blocked 4 Make sure that air lters are installed and clean 5 Manually turn the fans impellers and make sure they rotate freely 6 Check the internal fuse 7 Close the service panels...

Страница 11: ...per month Never use the dehumidi er without lters Rotor The rotor is maintenance free However for cleaning purposes it can be ushed out by compressed air A rotor cleaning procedure requires special k...

Страница 12: ...w danvex 1 0 Parts list Table 3 Name Number per dehumidi er Rotor drive motor 1 Condenser 1 Belt pulley 1 Rotor drive belt 1 Belt tensioner 1 Dehumidi ed air fan 1 Regeneration air fan 1 Heater 1 Roto...

Страница 13: ...ns when it supplies the Customer a repaired or a spare part Parts repair or replacement does not resultin the warranty period extension The parts and components replaced under the warranty belong to D...