01AUG 1005GB
Cat.20 / Tab. 05.91 / Page 05.06
DTC Mode 3:
Fig. 3:
In DTC Mode 3 the down-time cleaning procedure is started when the pressure comes under the
∆
p-
DTCmin limit, but only if the
∆
p-DTCmax has been exceeded. The terminals E1 and E2 are not taken
into account.
Cleaning in connection with the start/stop output (external
∆
p-
terminal):
The terminals D1 and D2 can be bridged with a potentialfree switch. The cleaning procedure
can be seen from the below table:
„
∆
p-Mode OFF“
Switch (terminals D1,D2)
Cleaning
open ON
closed OFF
„
∆
p-Mode ON“
Switch (terminals D1,D2)
Differential pressure
∆
p
Cleaning
open
∆
p >
∆
p MAX
ON
closed
∆
p >
∆
p MAX
OFF
open
∆
p <
∆
p MIN
OFF
closed
∆
p <
∆
p MIN
ON
Delta-P DTCmax