Error diagnostics 

 

Error 

Possible cause 

Recommended action 

LED 1.1 Fig. 1 is not illuminated 
and E1 and E2 are bridged. 

 

Power failure  

 

Fuse in controller defect  
 

 

The plant’s emergency stop is 
activated 

 

Internal control error 

 

Check the circuit voltage 

 

Check the fuses. 

 

Replace the fuse. 

 

Check the emergency stop.  
 

 

Contact Dantherm Filtration 
service 

No valve activation 

 

Defect lead connection  
 

 

Defect magnet coil 

 

Cycle interrupt 

 

Check cables and cable connec-
tions 

 

Replace magnet coil. 

 

Detach pressure difference me-
ter, change the settings and 
check the hose connections, etc.

No down-time-cleaning 

 

DTC cycle = 0 

 

No signal from fan  
(DTC mode 1-2) 

 

Set other value 

 

Apply signal to terminals E1 
and E2. 

The cleaning is inefficient 

 

Pause period too long 

 

Cleaning pressure too low 
 
 
 

 

Valve defect 

 

Pulse duration too short 
 

 

Cleaning cycle often disrupted 
 

 

Defect filter system 
 

 

Large-scale filters (>160 valves) 
where only a part of the filter is 
cleaned 

 

Reduce pause interval 04 

 

Adjust the pressure to 6-8 bar 
(min. 5 bar). 

 

Pause too short, so pressure is 
not reached. 

 

Check/replace valve. 

 

Can be modified in setting mode 
after consultation with Dan-
therm Filtration. 

 

Check pressure difference meter 
and hose connection. 

 

Check the filter’s operation in-
structions. 

 

Set the two main controllers to 
the same setting values. 

 

Check if 

-MAX and 

-

MIN switching points are set 
correctly. 

Faulty display of the pressure differ-
ence 

 

Failure in the hose connections 

 

Empty the hoses. 

 

Clean the hose connection on 
the filter housing with com-
pressed air (blow direction fil-
ter, never in sensor direction). 

 

Remove any bending on the 
hoses. 

 

Check the hoses inside the con-
trol unit for water, or the like. 

NF-8E / NF-16E alarm 

 

Valve setting wrong 

 

NF-8E / NF-16E controller de-
fect 

 

Check the number of valves 

 

Replace the defect controller 

 
 

Содержание NF-8HD

Страница 1: ...5 Vers 1005 CONTENTS Safety Instructions Tab 05 51 Page 06 01 06 02 Installation Manual Tab 05 91 Page 05 01 05 12 Operating Instructions Tab 05 91 Page 07 01 07 04 Maintenance Instructions Tab 05 91...

Страница 2: ...ction doors and similar may not be performed until after the usual cleaning periods have been run until filters are free of dust accumulation and dust waste has been carried to silo waste bin In this...

Страница 3: ...rotection must be provided against static electric charging in the suction arrangement Boring of holes in filter housing or adjoining pipe ducts may be performed only when the system has stopped and b...

Страница 4: ...air cleaning using 24V DC magnetic coils at the valves When the voltage supply is turned on the filter control automatically operates for previously specified cleaning periods without any need of ext...

Страница 5: ...nd the pressure afterwards reached the Delta P DTCmin limit Where the dust removal system includes automatic components these should also function during down time cleaning periods Signals for this pu...

Страница 6: ...0 ms 30 300ms 04 Interval time Interval time 10 4 500 s 05 DTC Interval time DT interval time 6s 2 100 s 06 Total valve no of valves 0 0 160 07 DTC Down Time Cl Down time cycles 6 0 32 08 DTCmax Param...

Страница 7: ...he differential pressure is displayed in plain text Test operation Go to the parameter test operation and select one of the following testmodes In Test mode 0 The test operation is de activated In Tes...

Страница 8: ...elected method DTC Mode 1 Fig 1 In DTC Mode 1 the down time cleaning procedure is started on the terminals E1 and E2 Fan stops E1 E2 open DTC Mode 2 Fig 2 In DTC Mode 2 the down time cleaning procedur...

Страница 9: ...are not taken into account Cleaning in connection with the start stop output external p terminal The terminals D1 and D2 can be bridged with a potentialfree switch The cleaning procedure can be seen f...

Страница 10: ...er the covers on the electrical controllers are properly and tightly mounted Specifications Application Specifications Terminals Mains voltage 230 V AC 10 110 V 120 V AC 10 1 3 2 3 Output voltage Appr...

Страница 11: ...V5 V6 V7 V8 B1 B2 B3 B4 24V DC Ventile 2 bis 8 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 S3 S4 V9 V10 V11 V12 V13 V14 V15 V16 _ F1 F2 24V DC Ventile 10 bis 16 24V DC 24V DC 3 1 3 2 3...

Страница 12: ...7 18 19 6 20 21 22 23 24 1 2 3 4 5 6 7 8 Y1 Y8 Y2 Y7 Y9 B1 B2 B3 B4 X1 X2 X3 X4 V1 V2 V3 V4 V5 V6 V7 V8 B1 B2 B3 B4 X1 X2 X3 X4 V1 V2 NF 8HD NF 16HD NF 8E NF 16E NF 8E NF 16E ON ON OFF OFF 1 2 3 4 5 6...

Страница 13: ...A3 S1 S2 E1 E2 D1 D2 L230 L110 NF 8HD M A1 A2 A1 L1 N A2 Fig 8 Connection of compressed air hoses for NF 8HD P1 P2 D04006 cdr 1 2 3 4 5 6 7 8 9 10 11 12 13 N 250 V AC 0 4 A Alarm ON OFF p extern ON O...

Страница 14: ...rameter value is saved To return to the operating mode Press the button and the button for more than 3 seconds to return to the operating mode Parameter list NF 8HD standard values in the p MIN 700 Pa...

Страница 15: ...01AUG 1005GB Cat 20 Tab 05 91 Page 05 012 D04008 cdr 3 s 3 s 1 s 1 s p 1 s p 2 s n max min 10 s t M M 5 s Fig 10 Short description of how to check and change the parameters...

Страница 16: ...efect Pulse duration too short Cleaning cycle often disrupted Defect filter system Large scale filters 160 valves where only a part of the filter is cleaned Reduce pause interval 04 Adjust the pressur...

Страница 17: ...V5 V6 V7 V8 B1 B2 B3 B4 24V DC Ventile 2 bis 8 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 S3 S4 V9 V10 V11 V12 V13 V14 V15 V16 _ F1 F2 24V DC Ventile 10 bis 16 24V DC 24V DC 3 1 3 2 3...

Страница 18: ...s to the voltage supply L230 1 L110 2 and N 3 or possibly another especially prescribed voltage In addition the safety recommendation NF10 must be observed Maintenance A stable operating filter contro...

Страница 19: ...has to be replaced Fuses Type T 0 4 A 250V DC 5x20 mm Main controller Type NF 8HD art no 388015 090 NF 16HD art no 388015 095 Extension unit Type NF 8E art no 388015 065 NF 16E art no 388015 067 Chip...

Отзывы: