State of Operation
The state of operation is indicated by the 3 light emitting diodes (LEDs) (Fig. 4, 1.1, 1.2, and
1.3) and the filter differential pressure is indicated in plain text.
LED 1.1
(ON): is illuminated if the unit is operational.
LED 1.2
(>
∆
p
MIN) is illuminated if the differential pressure is higher than
∆
p
MIN.
LED 1.3
(>
∆
p
MAX) is illuminated if the differential pressure is higher than
∆
p
MAX.
LED 1.1 + 1.2 + 1.3 flashes
: Alarm –
∆
p
MAX is exceeded.
Alarm - caused by other reasons
: is only indicated by the terminals A1, A2 and A3 (Fig. 5,
3.2).
∆
p-text field
: The differential pressure is displayed in plain text.
Test operation
Go to the parameter “test operation” and select one of the following testmodes:
In Test mode 0
The test operation is de-activated.
In Test mode 1
Testing the valves. The valves are tested one by one and are displayed in the text field.
In Test mode 2
The state of operation is displayed in the text field.
In Test mode 3
For technical purposes. The value for the AD-converter is displayed.
In Test mode 4-7
The LED’s and the relays are tested and displayed.
∆
p
-Mode
The
∆
p
-MIN and
∆
p
-MAX limits control the filter cleaning.
Setting of
∆
p
–MODE. See “ Displaying and setting parameters” – parameter no. 19.
If the cleaning procedure controlled by the differential pressure is de-activated, the following
text is displayed “Delta-P Mode OFF”.