49
060
78
3 •
V
ersi
on
1.
3 •
26
.04
.2
011
How to balance the unit
Introduction
This section will guide you through balancing HCV 3 and HCV 5.
Important
Only trained and certified technicians are allowed to balance the unit!
Legislation
Regulation of the air flow rates must always be carried out according to the national
legislation.
Only nominal air flow rate must be balanced. The nominal air flow rate corresponds to
Fan Step 3 in Manual Operation Mode on the control panel. See the other set points in
the section “Set points and control strategies” on page 53 and “Description of the con-
trol panel” in the user's guide.
When
Balancing of the unit must take place in the following situations:
•
Before the first operation of the unit
•
If the size of the house has been changed
•
If the house is renovated and the ducting system is affected by it
•
If the filter type is changed e.g. in connection with the pollen season
Before you start
All air dampers in the ducting system must be installed according to manufacturer rec-
ommendations before balancing of HCV 3 and HCV 5 take place.
Make sure that you have the following equipment ready before the installation starts:
•
Pressure manometer with approx. 5 mm diameter hose matching the pressure
adapter on the unit, which is 6 mm in diameter
•
Screwdriver with hex lobular pan head 25
Balancing the air
flows
When balancing the air volumes of HCV 3 and HCV 5 it is important to ensure that the
airflows are of equal mass flow!
Important:
The supply air flow (T2) must under no circumstances be higher than the extract air
flow (T3), as this can cause humid air to be pressed into the building construction, with
destructive, negative, effects on the building, if the vapour shield it not 100 % air tight
Procedure
Follow this procedure to balance the unit:
Step
Action
1
Dismount the bottom part of the front.
Make sure that the insulating cover
plates in front of the filters are cor-
rectly mounted with the soft side to-
wards the filter. Push the sheets
against the filter to avoid any air being
sucked in that way
Continued overleaf
Содержание HCV 3
Страница 2: ...2005 layout...
Страница 34: ...32 Dimensioner HCV 3 Aggregatets di mensioner Illustrationen viser dimensionerne p en HCV 3...
Страница 38: ...36 Appendiks A Ydelse og specifik ventilatoreffekt HCV 3 Forts ttes p n ste side...
Страница 40: ...38 Appendiks A Ydelse og specifik ventilatoreffekt fortsat HCV 5 Forts ttes p n ste side...
Страница 72: ...70 Dimensions HCV 3 Dimensions of the unit The illustration shows the dimensions of the HCV 3...
Страница 76: ...74 Appendix A Performance and specific fan effect HCV 3 Continued overleaf...
Страница 78: ...76 Appendix A Performance and specific fan effect continued HCV 5 Continued overleaf...
Страница 114: ...112 Abmessungen HCV 5 Abmessungen des Ger ts Die Abbildung zeigt die Abmessungen eines HCV 5...
Страница 122: ......
Страница 156: ...154 Dimensions HCV 3 Dimensions de l appareil L illustration indique les dimensions du mod le HCV 3...
Страница 160: ...158 Annexe A Performances et effect ventilateur sp cifique HCV 3 Suite la page suivante...
Страница 162: ...160 Annexe A Performances et effect ventilateur sp cifique suite HCV 5 Suite la page suivante...
Страница 165: ...2005 layout...