Set points and control strategies
Introduction
This section describes the different factory settings for HCV 3 and HCV 5 and the pos-
sibilities for adjustments on the control panel and the remote control.
Factory settings
Default factory settings:
Setup range
Set points
Factory
setting
HCP 4
Control panel
HRC 2
Remote
Fan Step 0
Off
-
-
Fan Step 1
Gear 14
Gear 1 - 41
Gear 1 - 71
Fan Step 2
Gear 39
Gear 21 -66
Gear 36 -81
Fan Step 3
Gear 64
Gear 46 - 91 Gear 46 - 91
Fan Step 4 (maximum speed)
Gear 100
Gear 100
From Fan
Step 3 to
Gear 100
10 – 30 gears
‘OFSET’
(gears between Fan Step1-2-3)
25 gears
-
-
Automatic cooling/bypass
Bypass, Tmax (extract temperature, T3)
Bypass, Tmin (outside temperature, T1)
T3
≥
24 °C
T1
≥
15 °C
-
-
*Of/22-30 °C
Of/8-15 °C
Automatic Demand Mode (RH%)
45%
45%
35-65%
Filter duration
180 days
180 days
90-360 days
Frost protection, exchanger
(see below)
Frost protection, after-heat
T4
≤
+ 2 °C
T2
≥
+ 5 °C
-
-
-
-
*)
Selecting ‘of’ eliminates automatic bypass.
Frost protection
The unit’s frost protection works as follows:
1) Frost protection of the exchanger.
The control strategy has a built-in frost protection preventing ice building up in the
heat exchanger.
If the exhaust air temperature (T4) is below + 2 °C for 1½ hours or longer, the unit
starts reducing the flow rate of supply air (i.e. RPM of the supply fan is reduced) until
the exhaust air temperature r 2 °C. Frost protection normally starts when
outdoor temperature (T1) reaches ÷ 6 - ÷ 7 °C, or below.
2) Unit shots down at an outside temperature below ÷ 13 °C
If the outside temperature (T1) is below ÷ 13 °C for more than 5 minutes, the unit will
stop operating for 30 minutes to prevent ice from building up. If the outside tempera-
ture does not reach a temperature above ÷ 13 °C, the units shots down for another
30 minutes, etc.
Continued overleaf
Содержание HCV 3
Страница 2: ...2005 layout...
Страница 34: ...32 Dimensioner HCV 3 Aggregatets di mensioner Illustrationen viser dimensionerne p en HCV 3...
Страница 38: ...36 Appendiks A Ydelse og specifik ventilatoreffekt HCV 3 Forts ttes p n ste side...
Страница 40: ...38 Appendiks A Ydelse og specifik ventilatoreffekt fortsat HCV 5 Forts ttes p n ste side...
Страница 72: ...70 Dimensions HCV 3 Dimensions of the unit The illustration shows the dimensions of the HCV 3...
Страница 76: ...74 Appendix A Performance and specific fan effect HCV 3 Continued overleaf...
Страница 78: ...76 Appendix A Performance and specific fan effect continued HCV 5 Continued overleaf...
Страница 114: ...112 Abmessungen HCV 5 Abmessungen des Ger ts Die Abbildung zeigt die Abmessungen eines HCV 5...
Страница 122: ......
Страница 156: ...154 Dimensions HCV 3 Dimensions de l appareil L illustration indique les dimensions du mod le HCV 3...
Страница 160: ...158 Annexe A Performances et effect ventilateur sp cifique HCV 3 Suite la page suivante...
Страница 162: ...160 Annexe A Performances et effect ventilateur sp cifique suite HCV 5 Suite la page suivante...
Страница 165: ...2005 layout...