2. Technical data
Model
CDS 80
CDS 100
CDS 200
Working area – temperature
°C
5 - 32
5 - 32
5 - 32
Working area - humidity
%RH
30 - 100
30 - 100
30 - 100
Air volume
m³/h
1600
2800
3000
Power supply
V/Hz
3x400/50
3x400/50
3x400/50
Max. ampere consumption without electric
heating element
A 5,8
9,1
13,7
Max. power consumption without electric
heating element
kW 2,5
3,8
6,4
Max. ampere consumption with electric
heating element
A 16,2
19,5
24,1
Max. power consumption with electric
heating element
kW 9,7
11,0
13,6
Refrigerant
R407C R407C
R407C
Quantity of refrigerant
kg
2,250
4,300
7,000
Sound level (1 m away from unit)
dB(A)
61
63
62
Weight kg
196
236
352
Protection class
IP
X2
X2
X2
2.1 Dimensions
The dimensions for CDS 80/100/200 are stated in section 11 “Dimension sketches”.
Dimensions for duct connections are stated in the table below – please also refer to section 11.
CDS 80 CDS 100 CDS 200
Duct connection air inlet mm 595 x 595 695 x 695 815 x 815
Duct connection air outlet mm 265 x 235 332 x 294 332 x 294
3. Installation of the unit
3.1. Positioning
When positioning the unit, be sure that the foundation is level to allow condensate water to run away from the drip
tray.
CAUTION!
Leave a free space of at least 60 cm
at the right side of the unit to ensure easy access to
carry out service on the dehumidifier