page 1 of 10
Oilbuner
Type Gulliver RG3D
GB
Technical instructions
Main components of the oilburner,
dimensions
Type
394 T1
Terminal power – output
68/88 – 188,5 kW (H
i
) (5,4/7,0 – 15 kg/h)
Fuel
Viscosity max. 6 mm
2
/s (1,5° E) at 20° C
Electrical supply
230 V +10% -15% 50 Hz
Electrical consumption
390 W
Capasitor
6,3 µF
Ignition transformer
Secondary: 8 kV 16 mA
Control box
550 SMD
Pump capacity
Max. 30 kg/h at 10 bar
Pump pressure
8 – 15 bar
Approval
MK 10.10/1255
1. Pump with pressure reducer
2. Electronic start delaying device
3. Control box
4. Reset button with lock-out lamp
5. Flange with insulating gasket
6. 2nd stage air damper adjustment assembly
7. Nozzle holder assembly
8. Photo resistance
9. Hydraulic jack
10 4 pole socket
11. 2nd stage valve
12. 1st stage valve
K:\framen\instrukt\Dantherm\RG\Engelsk\RG3D\RG3.fm-T1-021114-dm/lbk
Dimensions:
Main components of the oilburner:
228
142
Ø123
285
12
36
300
345
213
127
99
99
11
160
190
45˚
45˚
(All measurements are in mm)
Содержание 970930
Страница 1: ...Oilburner RG3D GB Code No 970930...