Register Byte
Database
parameter
Min
Max
De-
fault
Description
18
34
LP_mode
0
1
0
LP fail mode state
35
Sens_mode
0
1
0
Sensor fail mode state
19
36
HP_mode
0
1
0
HP fail mode state
37
Amb_mode
0
1
0
Ambient fail mode state
20
38
AmbT_
mode
0
1
0
Ambient temperature fail mode state
39
AmbRH_
mode
0
1
0
Ambient humidity fail mode state
21
40
SW Build
number
(high)
0
65535
x
SW build number
41
SW Build
number(low)
0
22
42
SW Version
(Major)
0
255
x
SW version major
43
SW Version
(Minor)
0
255
x
SW version minor
23
44
HP Alarm
Temp.
(Decimal)
0
99
60
HP fail occurs when Cond_temp1 is more then this
value.
Usage the same as for Evap_temp1.
45
HP Alarm
Temp.
(Fraction)
41
80
Fan_func-
tion
0
1
0
Enable FAN function in standby mode
81
42
82
Time_wait_
fan
60
7200
3600
Time to wait until FAN will be started in standby
mode, if enabled (seconds)
83
43
84
Time_run_
fan
15
600
60
Time to run FAN in standby mode if enabled (sec-
onds)
85
44
86
RH_Fen
0
1
0
Enable/disable Exhaust Fan function
87
Service_ena
0
1
0
Enable/disable Service interval function
45
88
Service_int
0
99
0
Service interval value in weeks
89
RS-485 Interface
Continued
Содержание 351510
Страница 9: ...9...
Страница 14: ...14 EN CDP 40 50 70 CDP 40T 50T 70T Dimensions...
Страница 18: ...18 EN CDP 40T 50T 70T Mounting and installation instructions CDP T 1...
Страница 19: ...19 EN Mounting and installation instructions CDP T Continued CDP 40T 2a CDP 50T 2b CDP 70T 2c...
Страница 20: ...20 EN 3 Mounting and installation instructions CDP T Continued...
Страница 35: ...35 EN Overview Accessories Water heating coil for CDP dehumidifier...
Страница 50: ...50 EN Spare parts 1 4 5 6 7 15 10 14 20 19 22 13 12 8 24 23 26 16 21 11 17 18 9 3 2 27 28 25...