Danfoss District Energy
VI.GP.P2.02
DKDHR
Instructions for installation and use
VX Solo II substations
13.0 Adjustment and commissioning, DHW Cylinder circuit
Domestic hot water
The VX Solo II substations types HWP and HWS are supplied with
connection pipes for domestic hot water cylinder on the primary
or secondary side.
The temperature in the DHW cylinder can be controlled by the
Danfoss ECL controller in combination with an ac valve.
Danfoss ECL Comfort 210/310
The application Key contains information about application, language
and factory settings, adapted to the type of system, for which it is
ordered.
Note! Various applications can be loaded.
The controller is factory-set for local language and the running time
for the actuator (DHW circuit) is preset for the actual application.
General controller settings such as “Time and Date” must be entered
during commissioning of the controller. And also the desired DHW
temperature must be set.
(Make sure that the immersion sensor is placed correctly before mak-
ing adjustment of the temperature).
Please refer to the enclosed manufacturer instructions for the ECL
210/310 controller in order to
set the required domestic hot water
temperature in the DHW cylinder circuit
:
ECL Application Key Box with ECL Comfort 210/310 user guide and
mounting guide, for further information.
We recommend that your order commissioning of the controller with
your local Danfoss Sales Company.
Below schedule states whether the VX Solo II is supplied with
connection pipes for DHW cylinder on the primary side or the se-
condary side, and whether the DHW temperature in the cylinder is
controlled by the electronic controller and also states the controller
application and the actuator/valve combination.
Please note:
Circulation pump for the domestic hot water on the secondary side of
the cylinder is not part of the delivery and must be mounted on site.
Type
Primary Connection for Cylinder
Secondary Connection for Cylinder
Pump for Cylinder Circuit
VX Solo II HWP
(ECL 210/A237), page 6
Control not part of delivery
VX Solo II HWP
(ECL 210/A247), page 7
Danfoss ECL 210, Application A247
+ AHQM / AMV 150
VX Solo II H2WP
(ECL 210/A260), page 8
Control not part of delivery
VX Solo II H2WP
(ECL 310/A377), page 9
Danfoss ECL 310, Application A377
+ AHQM / AMV 150
VX Solo II HWS
(ECL 210/A237), page 10
Danfoss ECL 210, Application A237
(AHQM / AMV 13)
Grundfos UPS 15-40
VX Solo II HWS
(ECL 210/A247), page 11
Danfoss ECL 210, Application A247
(AHQM / AMV 150)
Grundfos UPS 15-40
VX Solo II H2WS
(ECL 210/A267), page 12
Danfoss ECL 210, Application A267
(AHQM / AMV 13)
Grundfos UPS 15-40
Supply limit
Supply limit
VX Solo II with primary
connection for cylinder
VX Solo II with secondary
connection for cylinder