VLT
®
2800 Series
PNU
#
Parameter
description
Factory setting
4-setup
Conv.
index
Data
type
302
Digital input, term. 18
Start
Yes
0
5
303
Digital input, term. 19
Reversing
Yes
0
5
304
Digital input, term. 27
Reset and coast
inverse
Yes
0
5
305
Digital input, term. 29
Jog
Yes
0
5
307
Digital input, term. 33
No function
Yes
0
5
308
Term. 53, analogue input voltage
Reference
Yes
0
5
309
Term. 53, min scaling
0.0 V
Yes
-1
6
310
Term. 53, max scaling
10.0 V
Yes
-1
6
314
Term. 60, analogue input current
No function
Yes
0
5
315
Term. 60, min scaling
0.0 mA
Yes
-4
6
316
Term. 60, max scaling
20.0 mA
Yes
-4
6
317
Time out
10 sec.
Yes
-1
5
318
Function after timeout
No function
Yes
0
5
319
Term. 42, analogue output
0-I
MAX
= 0-20 mA
Yes
0
5
323
Relay output
Control ready
Yes
0
5
327
Pulse ref./FB
5000 Hz
Yes
0
7
341
Term. 46 digital output
Control ready
Yes
0
5
342
Term. 46 Max. pulse output
5000 Hz
Yes
0
6
343
Precise stop function
Normal ramp stop
Yes
0
5
344
Counter value
100000 pulses
Yes
0
7
349
Speed comp delay
10 ms
Yes
-3
6
4-Setup:
’
Yes
’
means that the parameter can be programmed
individually in each of the four Setups, i.e. one single
parameter can have four different data values.
’
No
’
means that the data value will be the same in all Setups.
Conversion index:
This number refers to a conversion figure to be used
when writing or reading via serial communication
with a frequency converter.
See
Data character
in
Serial communication
in the
Design Guide.
Data type:
Data type shows the type and length of the telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
MG.28.E9.02 - VLT is a registered Danfoss trademark
156