![Danfoss VT2800 Series Скачать руководство пользователя страница 151](http://html1.mh-extra.com/html/danfoss/vt2800-series/vt2800-series_design-manual_507920151.webp)
VLT
®
2800 Series
All about VLT
2800
■
Technical data, mains supply 3 x 380 - 480 V
According to international standards
Type
2805
2807
2811
2815
2822
2830
Output current
I
INV.
[A]
1.7
2.1
3.0
3.7
5.2
7.0
(3 x 380-480V)
I
MAX
(60s) [A]
2.7
3.3
4.8
5.9
8.3
11.2
Output power (400 V)
S
INV.
[KVA]
1.1
1.7
2.0
2.6
3.6
4.8
Typical shaft output
P
M,N
[kW]
0.55
0.75
1.1
1.5
2.2
3.0
Typical shaft output
P
M,N
[HP]
0.75
1.0
1.5
2.0
3.0
4.0
Max. cable cross
section, motor
[mm
2
/AWG]
1)
4/10
4/10
4/10
4/10
4/10
4/10
Input current
I
L,N
[A]
1.6
1.9
2.6
3.2
4.7
6.1
(3 x 380-480 V)
I
L,MAX
(60s)[A]
2.6
3.0
4.2
5.1
7.5
9.8
Max. cable cross
section, power
[mm
2
/AWG]
1)
4/10
4/10
4/10
4/10
4/10
4/10
Max. pre-fuses
IEC/UL
2)
[A]
20/20
20/20
20/20
20/20
20/20
20/20
Efficiency
3)
[%]
96
96
96
96
96
96
Power loss at 100%
load
[W]
28
38
55
75
110
150
Weight
[kg]
2.1
2.1
2.1
2.1
3.7
3.7
Enclosure
4
type
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
According to international standards
Type
2840
2855
2875
2880
2881
2882
Output current
I
INV.
[A]
9.1
12
16
24
32.0
37.5
(3 x 380-480V)
I
MAX
(60s) [A]
14.5
19.2
25.6
38.4
51.2
60.0
Output power (400 V)
S
INV.
[KVA]
6.3
8.3
11.1
16.6
22.2
26.0
Typical shaft output
P
M,N
[kW]
4.0
5.5
7.5
11.0
15.0
18.5
Typical shaft output
P
M,N
[HP]
5.0
7.5
10.0
15.0
20.0
25.0
Max. cable cross
section, motor
[mm
2
/AWG]
1)
4/10
4/10
4/10
16/6
16/6
16/6
Input current
I
L,N
[A]
8.1
10.6
14.9
24.0
32.0
37.5
(3 x 380-480 V)
I
L,MAX
(60s)[A]
13.0
17.0
23.8
38.4
51.2
60
Max. cable cross
section, power
[mm
2
/AWG]
1)
4/10
4/10
4/10
16/6
16/6
16/6
Max. pre-fuses
IEC/UL
2)
[A]
20/20
25/25
25/25
50/50
50/50
50/50
Efficiency
3)
[%]
96
96
96
97
97
97
Power loss at 100%
load
[W]
200
275
372
412
562
693
Weight
[kg]
3.7
6.0
6.0
18.5
18.5
18.5
Enclosure
4
type
IP20
IP20
IP20
IP20/
NEMA 1
IP20/
NEMA 1
IP20/
NEMA 1
1. American Wire Gauge. Max. cable cross
section is the largest cable cross section that can
be attached to the terminals. Always observe
national and local regulations.
2. Type gG pre-fuses must be used for installation
according to IEC rules. If you want to maintain
UL/cUL you must use pre-fuses of the type
Bussmann KTN-R 200 V, KTS-R 500 V or Ferraz
Shawmut, type ATMR (max. 30A). The fuses
must be placed for protection in a circuit that is
capable of supplying a maximum of 100,000 amps
RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured
motor cable with a rated load and rated frequency.
4. IP20 is standard for VLT 2805-2875,
whereas NEMA 1 is an option.
MG.28.E9.02 - VLT is a registered Danfoss trademark
151