16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter
group 15-1*). The logging buffer will never be full when
is set to
Log always
[0].
[0]
*
No
[1]
Yes
16-43 Timed Actions Status
View the timed actions mode.
Option:
Function:
[0]
*
Timed Actions Auto
[1]
Timed Actions Disabled
[2]
Constant On Actions
[3]
Constant Off Actions
16-49 Current Fault Source
Range:
Function:
0
*
[0 - 8 ] Value indicates source of current fault, including:
short circuit, over current and phase imbalance (from
left): [1-4] Inverter, [5-8] Rectifier, [0] No fault
recorded
After a short circuit alarm (imax2) or over current alarm
(imax1 or phase imbalance) this will contain the power card
number associated with the alarm. It only holds one number
so it will indicate the highest priority power card number
(master first). The value will persist on power cycle but if a
new alarm occurs it will be overwritten with the new power
card number (even if it a lower priority number). The value
will only be cleared when the alarm log is cleared (i.e. a 3-
finger reset would reset the readout to 0).
3.16.4 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0.0
*
[-200.0 - 200.0 ] View the total reference, the sum of digital,
analog, preset, bus and freeze references,
plus catch-up and slow-down.
16-52 Feedback [Unit]
Range:
Function:
0.000
ProcessCtrlUnit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of resulting
feedback value after
processing of Feedback 1-3
(see
and
par. 16-56) in the feedback
manager.
See par. 20-0*
Feedback
.
The value is limited by
settings in par. 20-13 and
par. 20-14. Units as set in
16-52 Feedback [Unit]
Range:
Function:
20-12 Reference/Feedback
Unit
.
16-53 Digi Pot Reference
Range:
Function:
0.00
*
[-200.00 - 200.00 ] View the contribution of the Digital
Potentiometer to the actual reference.
16-54 Feedback 1 [Unit]
Range:
Function:
0.000
ProcessCtrlUnit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of Feedback 1,
see par. 20-0*
Feedback
.
The value is limited by
settings in
and
20-14 Maximum Reference/
Feedb.
. Units as set in
20-12 Reference/Feedback
Unit
.
16-55 Feedback 2 [Unit]
Range:
Function:
0.000
ProcessCtrlUnit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of Feedback 2,
see par. 20-0*
Feedback
.
The value is limited by
settings in par. 20-13 and
par. 20-14. Units as set in
20-12 Reference/Feedback
Unit
.
16-56 Feedback 3 [Unit]
Range:
Function:
0.000
ProcessCtrlUnit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of Feedback 3,
see parameter group 20-0*
Feedback
.
The value is limited by
settings in
and
20-14 Maximum Reference/
Feedb.
. Units as set in
20-12 Reference/Feedback
Unit
.
16-58 PID Output [%]
Range:
Function:
0.0 %
*
[0.0 - 100.0 %] This parameter returns the Drive Closed
Loop PID controller output value in
percent.
Parameter Description
VLT
®
HVAC Drive Programming Guide
116