There are two options to connect an MCD200 to a Modbus network.
Option 1: Using an MCD Modbus Module (Cat. No: 175G9000)
Notes
A single Modbus Module is required for each MCD200.
•
Modbus Module settings are provided using two 8-way
•
DIP switches on the module.
Up to 31 Modbus Modules can be used as Modbus slave devices
•
on a single Modbus RTU network.
The Modbus Module is powered-up by the MCD200.
•
For more information about operating the MCD Modbus Module,
•
refer to the Installation Instructions (MG.17.Fx.02), located at
www.danfoss.com/drives.
B8
B7
B6
-
+
GND
MCD200
MCD
Modbus
Module
RS485
connection
onto a
Modbus
RTU
network
Cat. No: 175G9000
MCD200 Modbus Option