Type 1 protection requires that in the event of a short circuit on the
output of a soft starter the fault must be cleared without risk of injury to
personnel. The soft starter may or may not be operational after the fault.
Type 1 protection is provided by HRC fuses or a MCCB within the motor branch
circuit, which must be able to bear the required motor start current.
Typical selection criteria are as follows:
Rating (% Motor FLC),
Start Current
Starter
type
Protection Type
< 350% FLC
15 seconds
> 350% FLC
15 seconds
MCD200
Fuse (non time delayed)
175%
200%
Fuse (time delayed)
150%
175%
MCCB*
150 – 200%
MCD3000
Fuse (non time delayed)
150%
Fuse (time delayed)
125%
MCCB*
150 – 200%
* Consult the manufacturer’s specifi cation.
Maximum fuse ratings for Type 1 motor protection are specifi ed in UL
and IEC standards.
Fuse
Rating (% Motor FLC)
Fuse (non-time delayed)
300%
Fuse (time delayed)
175%
Short Circuit Protection: What is required for Type 1 short
circuit protection of a soft starter?