Safety functions
Test procedure
Approved
☑
Safe Stop 1 ramp based (SS1)
1. Safe Stop 1 function must be disabled
-
via DI1.
-
via DI2.
-
Check the Safe Stop 1 circuit connections against the circuit
diagram.
2. No safety faults and alarms.
3. Run the frequency converter.
4. Ensure that the correct frequency converter is running.
5. Select Safe Stop 1 while the frequency converter is running.
6. Check the following
-
The frequency converter ramps down to zero speed.
-
The motor is braked and stopped by the mechanical brake
(if available and configured).
-
The SS1 will end with an STO warning or alarm depending
on configuration.
7. Deselect Safe Stop 1.
8. Check the following
-
Safety Func. Pending is displayed.
-
Safe Stop 1 deselected and inactive.
9. Restart the frequency converter and check that the motor runs
normally.
10. Ensure that the Safe Stop 1 function is ready to operate.
11. Document and sign the commissioning test report.
Table 7.6 Commissioning Test Report, Safe Stop 1 Ramp Based