8.3.2 Vendor-specific Objects
The EtherNet/IP module supports vendor-specific classes 100, 101, 102, 103, and 104.
8.3.2.1 Class 100 ~ 102 Objects (Read/Write)
Class 100 ~ 102 objects allow parameter values to be read from and written to the soft starter.
Class 100d (0x64): Parameters 1–99
Class 101d (0x65): Parameters 100–199
Class 102d (0x66): Parameters 200~299
N O T I C E
Parameter lists vary according to the model and version of the soft starter. See the relevant soft starter operating guide for a
complete parameter list.
N O T I C E
When writing parameter values, the EtherNet/IP module will update all parameter values in the soft starter. Always enter a valid
value for every parameter.
N O T I C E
Changing the values of the Factory parameters (
parameter group 20-**)
may cause unpredictable behavior in the soft starter. Con-
sult a local supplier before adjusting the Factory parameters.
8.3.2.2 Class 103 Objects (Read Only)
Class 103d (0x67) allows soft starter state information to be read from the soft starter.
Table 6: Objects to be Read from the Soft Starter
Object name
Class
Instance
Attribute
Binary protocol version
103
100
100
Product type code
103
101
100
Reserved
103
102
100
Reserved
103
103
100
Soft starter model
103
104
100
Changed parameter number
103
105
100
Number of parameters
103
106
100
Changed parameter value
103
107
100
Reserved
103
108
100
Soft starter state
1 = Ready
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Restart delay (including temperature check)
6 = Tripped
7 = Programming mode
8 = Jog forward
103
109
100
AN427641276310en-000101 / 175R1187
26 | Danfoss A/S © 2022.10
Packet Structures
EtherNet/IP Module
Installation Guide