N O T I C E
The reset input is normally closed by default. If
parameter 3-8 Remote Reset Logic
is set to normally open, the reported state is
inverted (0 = closed, 1 = open).
N O T I C E
For models MCD5-0053B and smaller, current reported via communications is 10 times greater than the actual value (shown on
the LCP).
8.3.2.3 Class 104 Objects (Read Only)
Class 104d (0x68) allows extended information to be read from the soft starter.
Object name
Class
Instance
Attribute
Major software version - User interface
104
101
100
Minor software version - User interface
104
102
100
Major software version - Motor control
104
103
100
Minor software version - Motor control
104
104
100
Major software version - Remote LCP (if installed)
104
105
100
Minor software version - Remote LCP (if installed)
104
106
100
Major software version - Expansion card (if installed)
104
107
100
Minor software version -. Expansion card (if installed)
104
108
100
Model rating
104
109
100
Control variant
104
110
100
Backplane variant
104
111
100
Actual motor current
104
112
100
Variant high byte
104
113
100
Customer
104
114
100
8.3.3 Supported Services for Vendor-specific Objects
This section describes the operational instructions to carry out acyclic services on class objects 100, 101, 102, 103, and 104.
8.3.3.1 Service Codes for Acyclic Operation
Table 7: Supported Services for Vendor-specific Objects
Service code
Function
Description
01d (0x01)
Get attribute all
Only supported for class 0x01 identity object
10d (0x10)
Set attribute single
Supported
15d (0x0E)
Get attribute single
Supported
AN427641276310en-000101 / 175R1187
28 | Danfoss A/S © 2022.10
Packet Structures
EtherNet/IP Module
Installation Guide