10.2 General Technical Data
Mains supply
Supply Terminals (6-Pulse)
L1, L2, L3
Supply voltage
200-240 V
±
10%
Supply voltage
380-480 V/ 380-500 V
±
10%
: 525-600 V
±
10%
Supply voltage
: 525-690 V
±
10%
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the FC continues until the intermediate circuit voltage drops below the minimum
stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage. Power-up and full
torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. imbalance temporary between mains phases
3.0 % of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
ϕ
)
near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5kW
maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW
maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
90kW
maximum 1 time/2 min.
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/ 690
V maximum.
Motor output (U, V, W)
Output voltage
0 - 100% of supply voltage
Output frequency (0.25-75 kW)
: 0.2 - 1000 Hz/: 0 - 1000 Hz
Output frequency (90-1000 kW)
0 - 800
1)
Hz
Output frequency in Flux Mode ( only)
0 - 300Hz
Switching on output
Unlimited
Ramp times
0.01 - 3600 s
1)
Voltage and power dependent
Torque characteristics
Starting torque (Constant torque)
maximum 160% for 60 s.
1)
Starting torque
maximum 180% up to 0.5 sec.
1)
Overload torque (Constant torque)
maximum 160% for 60 s
1)
Starting torque (Variable torque)
maximum 110% for 60 s
1)
Overload torque (Variable torque)
maximum 110% for 60 s
Torque rise time in (independent of fsw)
10 ms
Torque rise time in FLUX (for 5 kHz fsw)
1 ms
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Cable lengths and cross sections for control cables
1)
Max. motor cable length, screened
: 50 m/ (A1): 25 m/ : 150 m
Max. motor cable length, unscreened
: 75 m/ (A1): 50 m/ : 300 m
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves
1.5 mm
2
/16 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves
1 mm
2
/18 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
0.5 mm
2
/20 AWG
Minimum cross section to control terminals
0.25 mm
2
/ 24AWG
1)
For power cables, see electrical data tables.
Specifications
VLT
®
HVAC Drive Operating Instructions
MG11AH02 - VLT
®
is a registered Danfoss trademark