2.1.14 Binary Output (BO) Commands (Not Acknowledged)
VLT
Response
Command
Region
NPA Object
no.
Attribute No. Attribute Message Type Error Code
Comments
NAK
1
4
0-10
6
Integer
Read Binary
Output
11
1)
Read Interstage on delay attrib-
ute associated with each
individual point. (JCI use only)
NAK
1
4
0-10
7
Integer
Read Binary
Output
11
1)
Read Interstage off delay attrib-
ute associated with each
individual point. (JCI use only)
NAK
2
4
0-10
2
Byte
Write Binary
Output
11
1)
Object Status not writeable
NAK
2
4
0-10
6
Integer
Write Binary
Output
11
1)
Write Interstage on delay attrib-
ute associated with each
individual point. (JCI use only)
NAK
2
4
0-10
7
Integer
Write Binary
Output
11
1)
Write Interstage off delay attrib-
ute associated with each
individual point. (JCI use only)
1)
Error code 11 is used because attributes are considered as fields/records in the point map database.
2.1.15 Internal Integers (ADI) Commands (Acknowledged)
VLT
Response
Command
Subcom-
mand
Region NPA Object no. Attribute No.
Attribute Message Type
Comments
ACK
1
-
6
0-254
1
Integer
Read Internal
Parameter of
object type
integer (16 bit)
Read Object Status associ-
ated with each individual
point
ACK
1
-
6
0-254
2
Integer
Read Internal
Parameter of
object type
integer (16bit)
Read Current Value attrib-
ute associated with each
individual point
ACK
2
-
6
0-254
-
Integer
Write Internal
Parameter of
object type
integer (16bit)
Write to Current Value
attribute associated with
each individual point
ACK
7
2
6
0-254
-
Integer Override Internal
Parameter of
object type
Integer (16 bit)
Write to internal parame-
ter current value (set-up
parameters for VLT)
ACK
7
3
6
0-254
-
-
Override Release Set the current value, the
value that it was before
the 1. Override Command
was issued
Instructions
VLT
®
Metasys
12
MG.11.G2.02 - VLT
®
is a registered Danfoss trademark
2
2