![Danfoss VLT HVAC Drive Metasys N2 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-metasys-n2/vlt-hvac-drive-metasys-n2_manual_3694510008.webp)
2.1.6. General Commands (Acknowledged)
VLT Re-
sponse
Com-
mand
Subcom-
mand
NPA Ob-
ject no.
Attribute Mes-
sage Type
Error
Code
Comments
ACK
0
4
-
Poll Message
No Acknowledge
-
The slave is to respond with any
data points, analog or binary I/O
that have been flagged for COS
ACK
0
5
-
Poll message
With Acknowledge
-
The slave is to respond with any
data points, analog or binary I/O
that have been flagged for COS
ACK
0
9
-
Status update Mes-
sage
-
Slave device must respond with de-
vice manufacturing model number
(Par. 621), days in service (Par.
600) and device status
ACK
F
-
-
Identify Device
Type
-
Slave device responds with an iden-
tification number of 10H to indicate
non JCI device
ACK
0
0
-
Synch Time
-
The internal clock is syncronized by
this command
ACK, no ac-
tion
8
0
-
Upload
-
Optional, no support in the fre-
quency converter
ACK, no ac-
tion
8
1
-
Upload
-
Optional, no support in the fre-
quency converter
ACK, no ac-
tion
8
3
-
Upload Record
-
Optional, no support in the fre-
quency converter
ACK, no ac-
tion
8
4
-
Upload Complete
-
Optional, no support in the fre-
quency converter
ACK, no ac-
tion
9
0
-
Download
-
Optional, no support in the fre-
quency converter
ACK, no ac-
tion
9
1
-
Download
-
Optional, no support in the fre-
quency converter
ACK, no ac-
tion
9
3
-
Download
-
Record optional, no support in the
frequency converter
ACK, no ac-
tion
9
4
-
Download Complete
-
Optional, no support in the fre-
quency converter
NAK
0
1
-
Read Memory
01
Slave device memory read based
on memory addresses
NAK
0
8
-
Warm Start
01
JCI use only
Table 2.1: No Region, Attribute Number and -type in this table.
2. Instructions
VLT
®
HVAC Drive Metasys N2
8
MG.11.G1.02 - VLT
®
is a registered Danfoss trademark
2
Содержание VLT HVAC Drive Metasys N2
Страница 2: ...1 Overview VLT HVAC Drive Metasys N2 2 MG 11 G1 02 VLT is a registered Danfoss trademark 1...
Страница 4: ...2 Instructions VLT HVAC Drive Metasys N2 4 MG 11 G1 02 VLT is a registered Danfoss trademark 2...
Страница 36: ...V Vlt Parameters 7 Index VLT HVAC Drive Metasys N2 36 MG 11 G1 02 VLT is a registered Danfoss trademark...