![Danfoss VLT HVAC Drive Metasys N2 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-metasys-n2/vlt-hvac-drive-metasys-n2_manual_3694510013.webp)
2.1.11. Binary Input (BI) Commands (Acknowledged)
VLT
Re-
sponse
Com-
mand
Sub-
com-
mand
Re-
gion
NPA Ob-
ject no.
Attribute
No.
Attribute Mes-
sage Type
Comments
ACK
1
-
2
0-135
1
Byte Read Bi-
nary In-
put
Read Object Con-
figuration attribute
associated with
each individual
point
ACK
1
-
2
0-135
2
Byte Read Bi-
nary In-
put
Read Object Status
attribute associ-
ated with each in-
dividual point
ACK
2
-
2
0-135
1
Byte Write Bi-
nary In-
put
Write to Object
Configuration at-
tribute associated
with each individu-
al point
ACK, no
action
7
2
2
0-135
-
Byte(
0/1)
Override
Binary In-
put
Binary inputs are
"outputs" from the
frequency convert-
er and should not
be written over by
the network con-
troller. (Status
word, Warnings,
and Alarms)
ACK, no
action
7
3
2
0-135
-
-
Overri-
deRelease
Binary inputs are
"outputs" from the
drive and should
not be written over
by the network
controller. (Status
word, Warnings
and Alarms)
ACK, no
action
7
7
2
0-135
-
-
Write Bi-
nary In-
put
Optional command
for slave devices.
Only Attributes
used for N2 com-
missioning purpo-
ses. Not to be im-
plemented at this
time
ACK, no
action
7
8
2
0-135
-
-
Read Bi-
nary In-
put
Optional command
for Attributes slave
devices. Only used
for N2 commission-
ing purposes. Not
to be implemented
at this time
VLT
®
HVAC Drive Metasys N2
2. Instructions
MG.11.G1.02 - VLT
®
is a registered Danfoss trademark
13
2
Содержание VLT HVAC Drive Metasys N2
Страница 2: ...1 Overview VLT HVAC Drive Metasys N2 2 MG 11 G1 02 VLT is a registered Danfoss trademark 1...
Страница 4: ...2 Instructions VLT HVAC Drive Metasys N2 4 MG 11 G1 02 VLT is a registered Danfoss trademark 2...
Страница 36: ...V Vlt Parameters 7 Index VLT HVAC Drive Metasys N2 36 MG 11 G1 02 VLT is a registered Danfoss trademark...