![Danfoss VLT HVAC Drive Metasys N2 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-metasys-n2/vlt-hvac-drive-metasys-n2_manual_3694510006.webp)
Illustration 2.1: Bus termination switch
In order to avoid potential equalizing currents in the screen, earth the cable screen via terminal
61, which is connected to the frame via an RC-link.
Bus termination: The RS485 bus must be terminated by a resistor network at both ends. For this
purpose, set switch S801 on the control card to "ON". For more information, see the paragraph:
Switches S201, S202 and S801.
NB!
Communication protocol must be set to FC MC par. 8-30.