Binary Inputs (BI), continued..
NPT
NPA
UNIT
DESCRIPTION
SELECTION
PARAMETER
NUMBER
BI
98
-
Off
0=FALSE
,
1=TRUE
16-94/95
BI
99
-
Local Reference
0=Remote ref.,
1
=Local ref.
16-94/95
BI
100
-
Running
0=FALSE
,
1=TRUE
16-94/95
BI
101
-
Running at refer-
ence
0=FALSE
,
1=TRUE
16-94/95
BI
102
-
Reverse direction
0=FALSE
,
1=TRUE
16-94/95
BI
103
-
Ramping
0=FALSE
,
1=TRUE
16-94/95
BI
104
-
Start forward re-
verse
0=FALSE
,
1=TRUE
16-94/95
BI
105
-
Adaptive tuning
running
0=FALSE
,
1=TRUE
16-94/95
BI
106
-
Adaptive tuning
finished
0=FALSE
,
1=TRUE
16-94/95
BI
107
-
Sleep mode
0=FALSE
,
1=TRUE
16-94/95
BI
108
-
Sleep boost
0=FALSE
,
1=TRUE
16-94/95
BI
109
-
Start delay
0=FALSE
,
1=TRUE
16-94/95
BI
110
-
OVC active (Auto
ramp)
0=FALSE
,
1=TRUE
16-94/95
BI
112
-
Reverse
0=FALSE
,
1=TRUE
16-80
BI
113
-
Setup MSB
0=FALSE
,
1=TRUE
16-80
BI
114
-
Setup LSB
0=FALSE
,
1=TRUE
16-80
BI
115
-
Catch up or Relay
04 Out 45
0=FALSE
,
1=TRUE
16-80
BI
116
-
Slow down or Re-
lay 01 Out 42
0=FALSE
,
1=TRUE
16-80
BI
117
-
Reserved, always
0.
0=FALSE
16-80
BI
118
-
Jog
0=FALSE
,
1=TRUE
16-80
BI
119
-
Reset
0=FALSE
,
1=TRUE
16-80
BI
120
-
Start
0=FALSE
,
1=TRUE
16-80
BI
121
-
Freeze output
0=FALSE
,
1=TRUE
16-80
BI
122
-
Q-stop
0=FALSE
,
1=TRUE
16-80
BI
123
-
Coast
0=FALSE
,
1=TRUE
16-80
BI
124
-
Switch 3 on in-
verse or DC brake
0=FALSE
,
1=TRUE
16-80
BI
125
-
Switch 2on inverse
or Preset ref. MSB
0=FALSE
,
1=TRUE
16-80
BI
126
-
Switch 1 on in-
verse or Preset
ref. LSB
0=FALSE
,
1=TRUE
16-80
BI
128
-
Terminal 33
0=FALSE
,
1=TRUE
16-60:0
BI
129
-
Terminal 32
0=FALSE
,
1=TRUE
16-60:1
BI
130
-
Terminal 29
0=FALSE
,
1=TRUE
16-60:2
BI
131
-
Terminal 27
0=FALSE
,
1=TRUE
16-60:3
BI
132
-
Terminal 19
0=FALSE
,
1=TRUE
16-60:4
BI
133
-
Terminal 18
0=FALSE
,
1=TRUE
16-60:5
BI
134
-
Terminal 37
0=FALSE
,
1=TRUE
16-60:6
BI
135
-
GPIO Terminal
X30/3
0=FALSE
,
1=TRUE
16-60:7
3. Appendix
VLT
®
HVAC Drive Metasys N2
26
MG.11.G1.02 - VLT
®
is a registered Danfoss trademark
3