0-06 GridType
Option:
Function:
[131] 525-600V/60Hz/Delta
[132] 525-600V/60Hz
0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast.
WARNING
Can cause PWM when coasted.
[0]
Off Function is not active.
[1]
*
On Function is active.
3.1.2 0-1* Define and Set Up Operations
A complete set of all parameters controlling the frequency
converter is called a set-up. The frequency converter
contains 2 set-ups: Set-up1 and Set-up2. Furthermore, a
fixed set of factory settings can be copied into one or
more set-ups.
Some of the advantages of having more than one set-up
in the frequency converter are:
•
Run motor in one set-up (Active Set-up) while
updating parameters in another set-up (Edit Set-
up)
•
Connect various motors (one at a time) to
frequency converter. Motor data for various
motors can be placed in different set-ups.
•
Rapidly change settings of frequency converter
and/or motor while motor is running e.g. Ramp
time or preset references) via bus or digital
inputs.
The Active Set-up can be set as Multi Set-up, where the
active set-up is selected via input on a digital input
terminal and/or via the bus control word.
Use
to copy a set-up to the other set-ups.
To avoid conflicting settings of the same parameter within
2 different set-ups, link the set-ups together using
. Stop the frequency converter before
switching between set-ups where parameters marked ‘not
changeable during operation’ have different values.
Parameters which are ‘not changeable during operation’
are marked FALSE in
.
0-10 Active Set-up
Option:
Function:
Select the set-up in which the frequency
converter is to operate.
[1]
*
Set-up 1
Set-up 1 is active.
[2]
Set-up 2
Set-up 2 is active.
[9]
Multi Set-
up
Is used for remote selection of set-ups using
digital inputs and the serial communication
port. This set-up uses the settings from
0-11 Programming Set-up
Option:
Function:
The number of the set-up being edited is
displayed in the LCP, flashing.
[1]
Set-up 1
Edit
Set-up 1
[2]
Set-up 2
Edit
Set-up 2
[9]
*
Active Set-up Edit parameters in the set-up selected via
digital I/Os
0-12 Link Setups
Option:
Function:
If the set-ups are not linked, a change between
them is not possible while the motor is running.
[0]
Not
linked
When selecting a different setup for operation,
the set-up change does not occur until the
motor is coasted
[20]
*
Linked
Copies “not changeable during operation”
parameters from one set-up to the other. It is
possible to switch set-up while the motor is
running.
3.1.3 0-3* LCP Custom Readout and Display
Text
It is possible to customise the display elements for various
purposes.
Custom Readout
The calculated value to be displayed is based on settings
in
(linear only),
,
4-14 Motor Speed High Limit [Hz]
and actual speed.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
21
3
3