Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
Liniar
units only
P 0-31
Motor Speed
130BB779.10
Motor Speed
High limit
P 4-14 (Hz)
Linear Unit (e
.g. Speed and flo
w)
Quadr
atic Unit (P
ressur
e)
Cubic Unit (P
ow
er)
Illustration 3.1 Custom Readout
The relation depends on the type of unit selected in
:
Unit Type
Speed Relation
Dimensionless
Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Quadratic
Power
Cubic
Table 3.1 Relation
0-30 Custom Readout Unit
Option:
Function:
Program a value to be shown in the
display of the LCP. The value has a linear,
squared or cubed relation to speed. This
relation depends on the unit selected (see
table above). The actual calculated value
can be read in
[0]
None
[1]
*
%
[5]
PPM
[10]
l/Min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m3/s
[24]
m3/min
[25]
m3/h
[30]
kg/s
0-30 Custom Readout Unit
Option:
Function:
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
Degree Celsius
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m Wg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[127] ft3/h
[140] ft/s
[141] ft/min
[160] Degree Fahr
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] hp
0-31 Custom Readout Min Value
Range:
Function:
0 CustomRea-
doutUnit
*
[ 0 -
999999.99
CustomRea-
doutUnit]
This parameter allows the
choice of the min. value of the
custom defined readout
(occurs at zero speed). It is
only possible to select a value
different to 0 when selecting a
linear unit in
. For Quadratic
and Cubic units the minimum
value is 0.
0-32 Custom Readout Max Value
Range:
Function:
100 CustomRea-
doutUnit
*
[ 0.0 -
999999.99
CustomRea-
doutUnit]
This parameter sets the
max value to be shown
when the speed of the
motor has reached the set
value for
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
22
MG18B302 - Rev. 2013-09-02