5.2.5 Control Terminals
IP20 200-240 V 0.25-11 kW and IP20 380-480 V 0.37-22 kW:
130BB622.10
Illustration 5.21 Location of Control Terminals
1.
Place a screwdriver behind the terminal cover to
activate snap.
2.
Tilt the screwdriver outwards to open the cover.
130BB624.10
Illustration 5.22 IP20 380-480 V 30-90 kW
1.
Place a screwdriver behind the terminal cover to
activate snap.
2.
Tilt the screwdriver outwards to open the cover.
Digital input 18, 19 and 27 mode is set in
5-00 Digital Input
Mode
(PNP is default value) and digital input 29 mode is
set in
5-03 Digital Input 29 Mode
(PNP is default value).
130BC249.10
Illustration 5.23 IP54 400 V 0.75-7.5 kW
1.
Remove the front cover.
Control terminals
shows all control terminals of the frequency
converter. Applying Start (term. 18), connection between
terminal 12-27 and an analog reference (term. 53 or 54
and 55) make the frequency converter run.
18 19
12 20 55
27 29 42 45 50 53 54
DIGI IN
DIGI IN
DIGI IN
DIGI IN
61 68 69
N
P
COMM. GND
+24V
0/4-20mA A OUT / DIG OUT
0/4-20mA A OUT / DIG OUT
GND
GND
10V/20mA IN
10V/20mA IN
10V OUT
130BB625.10
BUS TER.
OFF
ON
Illustration 5.24 Control Terminals
How to Install
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06
67
5
5