NOTICE
Mounting frequency converters in aggressive
environments increases the risk of stoppages and consid-
erably reduces the life of the frequency converter.
Before installing the frequency converter, check the
ambient air for liquids, particles, and gases. This is done by
observing existing installations in this environment. Typical
indicators of harmful airborne liquids are water or oil on
metal parts, or corrosion of metal parts.
Excessive dust particle levels are often found on instal-
lation cabinets and existing electrical installations. One
indicator of aggressive airborne gases is blackening of
copper rails and cable ends on existing installations.
2.5 Vibration and Shock
The frequency converter has been tested according to the
procedure based on the shown standards,
The frequency converter complies with requirements that
exist for units mounted on the walls and floors of
production premises, as well as in panels bolted to walls or
floors.
IEC/EN 60068-2-6
Vibration (sinusoidal) - 1970
IEC/EN 60068-2-64
Vibration, broad-band random
Table 2.2 Standards
2.6 Advantages
2.6.1 Why use a Frequency Converter for
Controlling Fans and Pumps?
A frequency converter takes advantage of the fact that
centrifugal fans and pumps follow the laws of propor-
tionality for such fans and pumps. For further information
see
2.6.3 Example of Energy Savings
.
2.6.2 The Clear Advantage - Energy Savings
The clear advantage of using a frequency converter for
controlling the speed of fans or pumps lies in the
electricity savings.
When comparing with alternative control systems and
technologies, a frequency converter is the optimum energy
control system for controlling fan and pump systems.
SYSTEM CURVE
FAN CURVE
PRESSURE%
130BA780.10
A
B
C
0
20
40
60
80
100
120
20
40
60
80
100
120
140
160
180
VOLUME%
Illustration 2.1 Fan Curves (A, B, and C) for Reduced Fan
Volumes
120
100
80
60
40
20
0
20
40
60
80
100
120
140
160
180
120
100
80
60
40
20
0
20
40
60
80
100 120
140
160 180
Voume %
Voume %
INPUT POWER %
PRESSURE %
SYSTEM CURVE
FAN CURVE
A
B
C
130BA781.10
ENERGY
CONSUMED
Illustration 2.2 When using a frequency converter to reduce
fan capacity to 60% - more than 50% energy savings may be
obtained in typical applications.
Product Overview
VLT
®
HVAC Basic Drive FC 101 Design Guide
12
MG18C502 - Rev. 2013-09-06
2
2
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT HVAC Basic Drive FC 101 www danfoss com drives...
Страница 2: ......
Страница 123: ...Index VLT HVAC Basic Drive FC 101 Design Guide MG18C502 Rev 2013 09 06 121...
Страница 124: ...www danfoss com drives MG18C502 130R0222 MG18C502 Rev 2013 09 05...