VLT
®
FCM Series
Programming
600 Operating data: Operating hours
(OPERATING HOURS)
Value:
Unit: hours
0.0 - 130,000.0
Function:
This parameter can be read out via the display or the
serial communication port. The value cannot be reset.
Description of choice:
Indicates the number of hours in which the FC
motor has been switched on.
The value is updated in the FC motor every hour
and saved when the unit is turned off.
601 Operating data: Hours run
(RUNNING HOURS)
Value:
Unit: hours
0.0 - 130,000.0
Function:
This parameter can be read out via the display
or the serial communication port. The value can
be reset via parameter 619.
Description of choice:
Indicates the number of hours in which the FC motor
has been in operation since reset in parameter 619.
The value is updated in the FC motor every hour
and saved when the unit is turned off.
603 Operating data: Number of power-up’s
(POWER UP’S)
Value:
Unit: number
0 - 9999
Function:
This parameter can be read out via the display
or the serial communication port.
Description of choice:
States the number of power-ups of the supply
voltage to the FC motor.
604 Operating data: Number of
overtemperatures
(OVER TEMP’S)
Value:
Unit: number
0 - 9999
Function:
This parameter can be read out via the display
or the serial communication port.
Description of choice:
States the number of temperature faults there
has been on the FC motor.
605 Operating data: Number of overvoltages
(OVER VOLT’S)
Value:
Unit: number
0 - 9999
Function:
This parameter can be read out via the display
or the serial communication port.
Description of choice:
States the number of overvoltages there has
been on the FC motor.
615 Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index XX - XXX]
Function:
Array type parameter. This parameter makes it possible
to see the reason why a trip occurs.
10 log values are stored.
The lowest log number (1) contains the latest/most
recently saved data value; the highest log number
(10) contains the oldest data value.
For additional information, see chapter on "
Warnings and alarms
".
Description of choice:
Read out as a figure code between 1 and 37.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.03.H3.02 - VLT is a registered Danfoss trademark
75