VLT
®
FCM Series
when parameter 002 has been set to
Local operation
[1], the motor is controlled via the digital inputs.
LCP control/as parameter 100
[3] is selected if the
reference is to be set via parameter 003.
LCP digital control/as parameter 100
[4] functions as
LCP control/as parameter 100
[3], although, when
parameter 002 has been set to
Local operation
[1], the
motor may be controlled via the digital inputs.
NB!:
Shift from Remote control to LCP digital
control and open loop:
The present motor frequency and direction of rotation
must be maintained. If the present direction of rotation
does not correspond to the reversing signal (negative
reference), the motor frequency f
M
will be set at 0 Hz.
Shift from LCP digital control and open loop
to Remote control:
The selected configuration (parameter 100)
will be active. Shifts are effected without
any abrupt movement.
Shift from
Remote control
to
LCP control/as parameter
100
or
LCP digital control/as parameter 100.
The present reference will be maintained. If the reference
signal is negative, the local reference will be set at 0.
Shift from
LCP control/as parameter 100
or
LCP
remote control as parameter 100
to
Remote control.
The reference will be replaced by the active reference
signal from the remote control..
014 Local stop
(LOCAL STOP)
Value:
Not possible (DISABLE)
[0]
✭
Possible (ENABLE)
[1]
Function:
This parameter disables/enables the local stop
function in question from the control panel. This
key is used when parameter 002 has been set
for
Remote control
[0] or
Local
[1].
Description of choice:
If
Disable
[0] is selected in this parameter, the
[STOP] key will be inactive.
NB!:
If
Enable
is selected, the [STOP] key
overrules all Start commands.
015 Local jog
(LOCAL JOGGING)
Value:
✭
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the jog function can be enabled/
disabled on the control panel.
Description of choice:
If
Disable
[0] is selected in this parameter, the
[JOG] key will be inactive.
016 Local reversing
(LOCAL REVERSING)
Value:
✭
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the reversing function can be
enabled/disabled on the control panel. This key can
only be used if parameter 002 has been set to
Local
operation
[1] and parameter 013 to
LCP control with
open loop
[1] or
LCP control as parameter 100
[3].
Description of choice:
If
Disable
[0] is selected in this parameter, the
[FWD/ REV] key will be inactive.
See parameter 200.
017 Local reset of trip
(LOCAL RESET)
Value:
Not possible (DISABLE)
[0]
✭
Possible (ENABLE)
[1]
Function:
In this parameter, the reset function can be
selected/removed from the keyboard. This key can
be used when parameter 002 has been set for
Remote control
[0] or
Local control
[1].
✭
= factory setting. () = display text [] = value for use in communication via serial communication port