VLT
®
FCD Series
Conversion:
Under the section entitled
Factory Settings
the vari-
ous attributes of each parameter are displayed. As a
parameter value can only be transferred as a whole
number, a conversion factor must be used to transfer
decimals.
Example:
Parameter 201
Output frequency, low limit f
MIN
has a
conversion factor of 0.1. If you wish to preset the
minimum frequency to 10 Hz, the value 100 must be
transferred, as a conversion factor of 0.1 means that
the value transferred is multiplied by 0.1. The value
100 will thus be perceived as 10.0.
Conversion table
Conversion
index
Conversion
factor
73
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
-5
0.00001
■
Process Words
The block of process words is divided into two
blocks of 16 bits, which always occur in the defined
sequence.
PCD 1
PCD 2
Control telegram
(master
⇒
slave)
Control word
Reference-
value
Control telegram
(slave
⇒
master)
Status word
Present outp.
frequency
MG.04.A1.02 - VLT is a registered Danfoss trade mark
99
Programming