Bit 09 = “0” means that ramp 1 is active (parameters
207/208). Bit 09 = “1” means that ramp 2 (parame-
ters 209/210) is active.
Bit 10, Data not valid/Data valid:
Is used to tell the frequency converter whether the
control word is to be used or ignored. Bit 10 = ’0’
causes the control word to be ignored, Bit 10 = ’1’
causes the control word to be used. This function is
relevant, because the control word is always con-
tained in the telegram, regardless of which type of
telegram is used, i.e. it is possible to turn off the
control word if you do not wish to use it in connec-
tion with updating or reading parameters.
Bit 11, No function:
Bit 11 has no function.
Bit 12, No function:
Bit 12 has no function.
Bit 13/14, Selection of Setup:
Bits 13 and 14 are used to choose from the four
menu Setups according to the following table:
Setup
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
The function is only possible when
Multi-Setups
is
selected in parameter 004
Active Setup
.
Note: I parameter 507
Selection of Setup
a selection
is made to define how Bit 13/14 gates with the corre-
sponding function on the digital inputs.
Bit 15 Reversing:
Bit 15 = ’0’ causes no reversing.
Bit 15 = ’1’ causes reversing.
Note: In the factory setting reversing is set to
digital
in parameter 506
Reversing
. Bit 15 only causes re-
versing when either
Ser. communication
,
Logic or
or
Logic and
is selected.
■
Status Word according toFC Profile
The status word is used to inform the master (e.g. a
PC) of the slave’s (frequency converter) mode.
Slave
⇒
Master.
Bit
Bit = 0
Bit =1
00
Control ready
01
Drive ready
02
Coasting stop
03
No trip
Trip
04
Not used
05
Not used
06
Not used
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local control
Ser. communi.
10
Outside
frequency range
Frequency limit
OK
11
Motor running
12
13
Voltage warn.
14
Current limit
15
Thermal warn.
Bit 00, Control ready:
Bit 00 = ’1’. The frequency converter is ready for op-
eration.
Bit 00 = ’0’. The frequency converter is not ready for
operation.
Bit 01, Drive ready:
Bit 01 = ’1’. The frequency converter is ready for op-
eration, but there is an active coasting command via
the digital inputs or via serial communication.
Bit 02, Coasting stop:
Bit 02 = ’0’. The frequency converter has released
the motor.
Bit 02 = ’1’. The frequency converter can start the
motor when a start command is given.
Bit 03, No trip/trip:
Bit 03 = ’0’ means that the frequency converter is
not in fault mode.