Description of choice:
If a time constant (t) of 100 ms is programmed, the
cut-off frequency for the lowpass filter will be 1/0.1 =
10 RAD/sec., corresponding to (10 / 2 x
) = 1.6 Hz.
The PID regulator will then only regulate a feedback
signal that varies with a frequency of less than 1.6
Hz. If the feedback signal varies by a higher fre-
quency than 1.6 Hz, it will be dampened by the
lowpass filter.
423
423 U1 voltage
(U1 VOLTAGE)
Value:
0.0 - 999.0 V
✭
par. 103
Function:
Parameters 423-428 are used when in parameter
101
Torque characteristic
a selection has been made
of
Special motor characteristic
[8]. It is possible to
determine a U/f characteristic on the basis of four
definable voltages and three frequencies. The volt-
age at 0 Hz is set in parameter 133
Start voltage
.
Description of choice:
Set the output voltage (U1) that is to match the first
output frequency (F1), parameter 424
F1 frequency
.
424
424 F1 frequency
(F1 FREQUENCY)
Value:
0.0 - par. 426
F2 frequency
✭
Par. 104
Motor frequency
Function:
See parameter 423
U1 voltage
.
Description of choice:
Set the output frequency (F1) that is to match the
first output voltage (U1), parameter 423
U1 voltage
.
425
425 U2 voltage
(U2 VOLTAGE)
Value:
0.0 - 999.0 V
✭
par. 103
Function:
See parameter 423
U1 voltage
.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.A1.02 - VLT is a registered Danfoss trade mark
89