26-44 Terminal X42/7 Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %] Holds the preset level of terminal X42/7.
In case of a bus timeout and a timeout
function is selected in
the output will preset to this level.
3.20.6 26-5* Analog Input X42/9
26-50 Terminal X42/9 Output
Option:
Function:
Set the function of terminal X42/9.
[0]
*
No operation
[100] Output frequency
0-100 Hz, (0-20 mA)
[101] Reference
Minimum reference - Maximum
reference, (0-20 mA)
[102] Feedback
-200% to +200% of
3-03 Maximum
Reference
, (0-20 mA)
[103] Motor Current
0 - Inverter Max. Current (
), (0-20 mA)
[104] Torque rel to limit 0 - Torque limit (
), (0-20 mA)
[105] Torq relate to
rated
0 - Motor rated torque, (0-20 mA)
[106] Power
0 - Motor rated power, (0-20 mA)
[107] Speed
0 - Speed High Limit (
and
), (0-20 mA)
[108] Torque
[109] Max Out Freq
[113] Ext. Closed Loop 1 0 - 100%, (0-20 mA)
[114] Ext. Closed Loop 2 0 - 100%, (0-20 mA)
[115] Ext. Closed Loop 3 0 - 100%, (0-20 mA)
[139] Bus ctrl.
0 - 100%, (0-20 mA)
[141] Bus ctrl t.o.
0 - 100%, (0-20 mA)
26-51 Terminal X42/9 Min. Scale
Range:
Function:
0 %
*
[0 - 200
%]
Scale the minimum output of the selected
analog signal at terminal X42/9, as a percentage
of the maximum signal level. E.g. if a 0 V is
desired at 25% of the maximum output value.
Then programme 25%. Scaling values up to
100% can never be higher than the
corresponding setting in
.
See principle graph for
6-51 Terminal 42 Output Min Scale
26-52 Terminal X42/9 Max. Scale
Range:
Function:
100
%
*
[0 -
200
%]
Scale the maximum output of the selected analog
signal at terminal X42/9. Set the value to the
maximum value of the voltage signal output. Scale
the output to give a voltage lower than 10 V at
full scale; or 10 V at an output below 100% of the
maximum signal value. If 10 V is the desired
output current at a value between 0-100% of the
full-scale output, programme the percentage value
in the parameter, i.e. 50% = 10 V. If a voltage
between 0 and 10V is desired at maximum output,
calculate the percentage as follows:
i.e.
5
V : 10V
5
V x100 % = 200 %
See principle graph for
6-52 Terminal 42 Output Max Scale
26-53 Terminal X42/9 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of terminal X42/9 if
controlled by bus.
26-54 Terminal X42/9 Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %] Holds the preset level of terminal X42/9.
In case of a bus timeout and a timeout
function is selected in
the output will preset to this level.
3.20.7 26-6* Analog Input X42/11
26-60 Terminal X42/11 Output
Option:
Function:
Set the function of terminal X42/11.
[0]
*
No operation
[100] Output frequency
0-100 Hz, (0-20 mA)
[101] Reference
Minimum reference - Maximum
reference, (0-20 mA)
[102] Feedback
-200% to +200% of
3-03 Maximum
Reference
, (0-20 mA)
[103] Motor Current
0 - Inverter Max. Current (
), (0-20 mA)
[104] Torque rel to limit
0 - Torque limit (
), (0-20 mA)
[105] Torq relate to rated 0 - Motor rated torque, (0-20 mA)
[106] Power
0 - Motor rated power, (0-20 mA)
[107] Speed
0 - Speed High Limit (
and
), (0-20 mA)
[108] Torque
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
162
MG16H102 - VLT
®
is a registered Danfoss trademark
3