5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
•
Each terminal has specified functions it is capable
of performing.
•
Parameters associated with the terminal enable
the function.
•
For proper adjustable frequency drive
functioning, the control terminals must be
wired properly
programmed for the intended function
receiving a signal
See
for control terminal parameter number and
default setting. (Default setting can change based on the
selection in
0-03 Regional Settings
).
The following example shows accessing Terminal 18 to see
the default setting.
1.
Press [Main Menu] twice, scroll to parameter
group
5-** Digital In/Out
and press [OK].
130B
T768.10
2-** Brakes
3-** Reference / Ramps
4-** Limits / Warnings
5-** Digital In/Out
14.6% 0.00A 1(1)
Main Menu
Figure 5.9
2.
Scroll to parameter group
5-1* Digital Inputs
and
press [OK].
130B
T769.10
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
14.7% 0.00A 1(1)
Digital In/Out
5-**
Figure 5.10
3.
Scroll to
5-10 Terminal 18 Digital Input
. Press [OK]
to access function choices. The default setting
Start
is shown.
5-1*
130B
T770.10
5-10 Terminal 18 Digital
Input
[
8
]] Start
14.7% 0.00A 1(1)
Digital Inputs
Figure 5.11
5.4 International/North American Default
Parameter Settings
Setting
0-03 Regional Settings
to
[0] International
or
[1]
North America
changes the default settings for some
parameters.
lists those parameters that are
effected.
Parameter
International
default parameter
value
North American
default parameter
value
0-03 Regional
Settings
International
North America
0-71 Date Format
DD-MM-YYYY
MM/DD/YYYY
0-72 Time Format
24 h
12 h
1-20 Motor Power
[kW]
See Note 1
See Note 1
1-21 Motor Power
[HP]
See Note 2
See Note 2
1-22 Motor Voltage 230 V/400 V/575 V
208 V/460 V/575 V
1-23 Motor
Frequency
50 Hz
60 Hz
3-03 Maximum
Reference
50 Hz
60 Hz
3-04 Reference
Function
Sum
External/Preset
4-13 Motor Speed
High Limit [RPM]
See Note 3
1500 RPM
1800 RPM
4-14 Motor Speed
High Limit [Hz]
See Note 4
50 Hz
60 Hz
4-19 Max Output
Frequency
100 Hz
120 Hz
4-53 Warning Speed
High
1500 RPM
1800 RPM
5-12 Terminal 27
Digital Input
Coast inverse
External interlock
Programming
VLT
®
Refrigeration Drive Instruction Manual
MG16J122 - VLT
®
is a registered Danfoss trademark
5-3
5
5
Содержание VLT FC 103
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT Refrigeration Drive FC 103 75 400 kW ...
Страница 2: ......
Страница 4: ...Safety VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark ...
Страница 8: ...Contents VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark ...
Страница 93: ...Index VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark 12 5 ...
Страница 94: ...www danfoss com drives MG16J122 130R0414 MG16J122 Rev 2013 04 22 ...