5 Programming
5.1 Introduction
The adjustable frequency drive is programmed for its
application functions using parameters. Parameters are
accessed by pressing either [Quick Menu] or [Main Menu]
on the LCP. (See
for details on using
the LCP function keys). Parameters may also be accessed
through a PC using the MCT 10 Set-up Software (see
5.6.1 Remote Programming with MCT 10 Set-up Software
The quick menu is intended for initial startup (
Q2-** Quick
Set-up
) and detailed instructions for common adjustable
frequency drive applications (
Q3-** Function Set-up
). Step-
by-step instructions are provided. These instructions enable
the user to walk through the parameters used for
programming applications in their proper sequence. Data
entered in a parameter can change the options available in
the parameters following that entry. The quick menu
presents easy guidelines for getting most systems up and
running.
The main menu accesses all parameters and allows for
advanced adjustable frequency drive applications.
5.2 Programming Example
Here is an example for programming the adjustable
frequency drive for a common application in open-loop
using the quick menu.
•
This procedure programs the adjustable
frequency drive to receive a 0–10 V DC analog
control signal on input terminal 53
•
The adjustable frequency drive will respond by
providing 6–60 Hz output to the motor propor-
tional to the input signal (0–10 V DC = 6–60 Hz)
Select the following parameters using the navigation keys
to scroll to the titles and press [OK] after each action.
1.
3-15 Reference Resource 1
5-1*
130BB848.10
3-15 Reference Resource
[
1
]] Analog input 53
14.7% 0.00A 1(1)
References
Figure 5.1
2.
3-02 Minimum Reference
. Set minimum internal
adjustable frequency drive reference to 0 Hz.
(This sets the minimum adjustable frequency
drive speed at 0 Hz.)
Q3-21
130B
T762.10
3-02 Minimum Reference
0.000 Hz
14.7% 0.00A 1(1)
Analog Reference
Figure 5.2
3.
3-03 Maximum Reference
. Set maximum internal
adjustable frequency drive reference to 60 Hz.
(This sets the maximum adjustable frequency
drive speed at 60 Hz. Note that 50/60 Hz is a
regional variation.)
Q3-21
130B
T763.11
3-03 Maximum Reference
50.000 Hz
14.7% 0.00A 1(1)
Analog Reference
Figure 5.3
Programming
VLT
®
Refrigeration Drive Instruction Manual
MG16J122 - VLT
®
is a registered Danfoss trademark
5-1
5
5
Содержание VLT FC 103
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT Refrigeration Drive FC 103 75 400 kW ...
Страница 2: ......
Страница 4: ...Safety VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark ...
Страница 8: ...Contents VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark ...
Страница 93: ...Index VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark 12 5 ...
Страница 94: ...www danfoss com drives MG16J122 130R0414 MG16J122 Rev 2013 04 22 ...