Service Manual FCD 300
Release 01/2003
30
Revise 08/01/2003 by DD Service Manager, Steffen Sundbæk
19.4. Digital outputs
Digital output have PNP open collector output static signal, totem pole for pulse signals.
Digital output current is max. 25 mA continuous and 50 mA for short time, 13 ms.
The output is short circuit protected and protected against voltage transients caused by
inductive loads.
If the digital output is overloaded, it will be turned off after 13 ms and once a second the
output will be activated again.
19.5. LCP cable length
Max. distance between LCP2 and FCD300: 3 m.
20.
Voltage level overview
Voltage level description
(DC link voltage)
Inverter Over voltage Disable
820 V
Inverter Over voltage Enable
805 V
Voltage High Warning with Brake
800 V
Brake Start
770 V
Voltage High Warning Without Brake
765 V
Inverter Under voltage Enable & Inrush Enable
450 V
Voltage Low Warning
440 V
Inverter Under voltage Disable & Inrush Disable
410 V
Voltage trip times
Time in over voltage before trip
5 or 15 times within 10ms
Time in under voltage before trip
2,5 sec
21.
Current levels
Current level description
Short circuit (and earth short circuit fault)
260% Inom
Time in short circuit before trip (inverter disable)
5 – 8
µ
s
Over current (hardware)
210% Inom
Time in over current before trip
2 – 4 sec
Earth fault
4 –5 A
Time in earth fault before trip (inverter disable)
5 – 8
µ
s
Software current limit
160% Inom
Time in software current limit before trip
60 sec