3 Parameters
3.1 Main Menu - Operation and Display -
Group 0
0-01 Language
Defines the language to be used in the display.
Option:
Function:
[0]
*
English
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
[255]
No Text
0-04 Operating State at Power-up
Select the operating mode after reconnection of the frequency
converter to mains voltage after power-down when operating in
Hand (local) mode
.
Option:
Function:
[0]
*
Resume
Resumes operation of the
frequency converter, maintaining
the same local reference and the
same start/stop condition (applied
by [Hand On]/[Off] on the LCP or
local start via a digital input) as
before the frequency converter was
powered down.
[1]
Forced stop,
ref=old
Uses saved reference [1] to stop the
frequency converter, but at the
same time retains the local speed
reference in memory before
powering down. After mains
voltage is reconnected, and after
receiving a start command
(pressing [Hand On] key or using
the local start command via a
digital input), the frequency
converter restarts and operates at
the retained speed reference.
0-06 GridType
Select the grid type of the supply voltage/frequency.
IT grid is a supply mains, where there are no connections to
ground.
Delta is a supply mains where the secondary part of the
transformer is delta connected and one phase is connected to
ground.
Option:
Function:
NOTICE
Not all options are supported
in all power sizes.
[0]
200-240V/
50Hz/IT-grid
[1]
200-240V/
50Hz/Delta
[2]
200-240V/
50Hz
[10]
380-440V/
50Hz/IT-grid
[11]
380-440V/
50Hz/Delta
[12]
380-440V/
50Hz
[20]
440-480V/
50Hz/IT-grid
[21]
440-480V/
50Hz/Delta
[22]
440-480V/
50Hz
[30]
525-600V/
50Hz/IT-grid
[31]
525-600V/
50Hz/Delta
[32]
525-600V/
50Hz
[100]
200-240V/
60Hz/IT-grid
[101]
200-240V/
60Hz/Delta
[102]
200-240V/
60Hz
[110]
380-440V/
60Hz/IT-grid
[111]
380-440V/
60Hz/Delta
[112]
380-440V/
60Hz
[120]
440-480V/
60Hz/IT-grid
Parameters
VLT
®
Compressor Drive CDS 803
18
Danfoss A/S © 06/2019 All rights reserved.
MG18P202
3
3