Enclosure Size
H3
H4
H5
H6
e
5.5 (0.22)
7 (0.28)
7 (0.28)
8.5 (0.33)
f
8.1 (0.32)
8.4 (0.33)
8.5 (0.33)
15 (0.6)
Maximum weight kg (lb)
4.5 (9.9)
7.9 (17.4)
9.5 (20.9)
5.3 (11.7)
1
Including decoupling plate.
The dimensions are only for the physical units. When installing in an application, allow space above and below the units for cooling.
The amount of space for free air passage is listed in
4.9.2 Shipping Dimensions
Table 8: Shipping Dimensions
Enclo-
sure size
200–240 V AC
[kW (hp)]
380–480 V AC [kW
(hp)]
IP rat-
ing
Maximum
weight [kg (lb)]
Height [mm
(in)]
Width [mm
(in)]
Depth [mm
(in)]
H3
–
6.0–7.5 (8.0–10)
IP20
4.5 (9.9)
280 (11)
155 (6.1)
320 (12.6)
H4
6.0–7.5 (8.0–10)
10 (15)
IP20
7.9 (17.4)
380 (15)
200 (7.9)
315 (12.4)
H5
10 (15)
18.5–22 (25–30)
IP20
9.5 (20.9)
395 (15.6)
233 (9.2)
380 (15)
H6
–
30 (40)
IP20
24.5 (54.0)
850 (33.5)
370 (15.6)
460 (18.1)
4.10 dU/dt
Table 9: dU/dt Data
Cable length [m (ft)]
AC line voltage [V]
Rise time [μsec]
V
peak
[kV]
dU/dt [kV/μsec]
200 V 6.0 kW (8.0 hp)
5 (16)
240
0.128
0.445
2.781
25 (82)
240
0.224
0.594
2.121
50 (164)
240
0.328
0.596
1.454
200 V 7.5 kW (10 hp)
5 (16)
240
0.18
0.502
2.244
25 (82)
240
0.22
0.598
2.175
50 (164)
240
0.292
0.615
1.678
200 V 10 kW (15 hp)
36 (118)
240
0.176
0.56
2.545
50 (164)
240
0.216
0.599
2.204
400 V 6.0 kW (8.0 hp)
5 (16)
400
0.168
0.81
3.857
25 (82)
400
0.239
1.026
3.434
50 (164)
400
0.328
1.05
2.560
400 V 7.5 kW (10 hp)
5 (16)
400
0.168
0.81
3.857
25 (82)
400
0.239
1.026
3.434
50 (164)
400
0.328
1.05
2.560
400 V 18.5 kW (25 hp)
5 (16)
400
0.132
0.88
5.220
25 (82)
400
0.172
1.026
4.772
AJ330233902305en-000201 / 130R0596
34 | Danfoss A/S © 2021.05
Specifications
VLT® Compressor Drive CDS 803
Design Guide