e3
0b
i9
25
.1
0
0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100 %
110 %
0
2
4
10
6
50 °C
45 °C
40 °C
I
out
[%]
f
sw
[kHz ]
8
12
Illustration 24: 400 V IP20 H6 30 kW (40 hp)
5.3.6 Derating for Low Air Pressure and High Altitudes
The cooling capability of air is decreased at low air pressure. For altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV.
Below 1000 m (3281 ft) altitude, derating is not necessary. For altitudes above 1000 m (3281 ft), decrease the ambient temperature
or the maximum output current. Decrease the output by 1% per 100 m (328 ft) altitude above 1000 m (3281 ft) or reduce the maxi-
mum ambient cooling air temperature by 1 °C (1.8 °F) per 200 m (656 ft).
5.4 IP21/NEMA Type 1 Enclosure Kit
If environment, air quality, or surroundings require extra protection, an IP21/NEMA Type 1 kit can be ordered, see
unit is upgraded to comply with enclosure IP21/NEMA Type 1.
N O T I C E
The IP21/IP21 are not suitable for outdoor mounting.
AJ330233902305en-000201 / 130R0596 | 41
Danfoss A/S © 2021.05
Mechanical Installation
Considerations
VLT® Compressor Drive CDS 803
Design Guide
Содержание VLT CDS 803
Страница 1: ...Design Guide VLT Compressor Drive CDS 803 6 30 kW vlt drives danfoss com...
Страница 2: ......