7.3  Warning and Alarm Code List

An (X) marked in 

Table 7.1

 indicates that the warning or alarm has occurred. A warning precedes an alarm.

Numb
er

Description

Warning

Alarm

Trip lock

Cause

2

Live zero error

X

X

Signal on terminal 53 or 54 is less than 50% of value set
in 

parameter 6-10 Terminal 53 Low Voltage

,

parameter 6-12 Terminal 53 Low Current

,

parameter 6-20 Terminal 54 Low Voltage

, and

parameter 6-22 Terminal 54 Low Current

.

3

No motor

X

No motor has been connected to the output of the
frequency converter, or 1 motor phase is missing.

4

Mains phase loss

1)

X

X

X

Missing phase on supply side, or the voltage imbalance is
too high. Check the supply voltage.

7

DC overvoltage

1)

X

X

Intermediate circuit voltage exceeds limit.

8

DC undervoltage

1)

X

X

Intermediate circuit voltage drops below the voltage
warning low limit.

9

Inverter overloaded

X

X

More than 100% load for too long.

10

Motor ETR overtemperature

X

X

Motor is too hot due to more than 100% load for too
long.

11

Motor thermistor overtem-
perature

X

X

Thermistor or thermistor connection is disconnected.

12

Torque limit

X

X

Torque exceeds value set in either 

parameter 4-16 Torque

Limit Motor Mode

 or 

parameter 4-17 Torque Limit Generator

Mode

.

13

Overcurrent

X

X

X

Inverter peak current limit is exceeded. For J1–J6 units, if
this alarm occurs on power-up, check whether power
cables are mistakenly connected to the motor terminals.

14

Earth fault

X

X

Discharge from output phases to ground.

16

Short circuit

X

X

Short circuit in motor or on motor terminals. For J7 units,
if this alarm occurs on power-up, check whether power
cables are mistakenly connected to the motor terminals.

17

Control word timeout

X

X

No communication to frequency converter.

18

Start failed

X

25

Brake resistor short-circuited

X

X

Brake resistor is short-circuited, thus the brake function is
disconnected.

26

Brake overload

X

X

The power transmitted to the brake resistor over the last
120 s exceeds the limit. Possible corrections: Decrease
brake energy via lower speed or longer ramp time.

27

Brake IGBT/Brake chopper short-
circuited

X

X

Brake transistor is short-circuited, thus brake function is
disconnected.

28

Brake check

X

Brake resistor is not connected/working.

30

U phase loss

X

X

Motor phase U is missing. Check the phase.

31

V phase loss

X

X

Motor phase V is missing. Check the phase.

32

W phase loss

X

X

Motor phase W is missing. Check the phase.

34

Fieldbus fault

X

X

PROFIBUS communication issues have occurred.

35

Option fault

X

Fieldbus or option B detects internal faults.

36

Mains failure

X

X

This warning/alarm is only active if the supply voltage to
the frequency converter is lost and 

parameter 14-10 Mains

Failure

 is NOT set to 

[0] No Function

.

38

Internal fault

X

X

Contact the local Danfoss supplier.

40

Overload T27

X

Check the load connected to terminal 27 or remove
short-circuit connection.

Diagnostics and Troubleshoo...

Quick Guide

MG06A702

Danfoss A/S © 03/2017 All rights reserved.

47

7

7

Содержание VLT AutomationDrive FC 360

Страница 1: ...ENGINEERING TOMORROW Quick Guide VLT AutomationDrive FC 360 vlt drives danfoss com...

Страница 2: ......

Страница 3: ...eneral Requirements 13 4 2 EMC compliant Installation 13 4 3 Grounding Requirements 13 4 4 Wiring Schematic 15 4 5 Mains Motor and Ground Connections 17 4 6 Control Wiring 18 4 7 Jumper Terminals 12 a...

Страница 4: ...and Alarm Code List 47 7 4 Error Code List 51 7 5 Troubleshooting 51 8 Specifications 53 8 1 Mains Supply 3x380 480 V AC 53 8 2 General Technical Data 56 8 3 Fuses 60 8 4 Connection Tightening Torques...

Страница 5: ...for improvement are welcome Edition Remarks Software version MG06A7 Update due to new software release 1 70 1 4 Approvals and Certifications 1 5 Disposal Do not dispose of equipment containing electri...

Страница 6: ...nics on the AC input Area Component Functions 5 Capacitor bank Stores the DC power Provides ride through protection for short power losses 6 Inverter Converts the DC into a controlled PWM AC waveform...

Страница 7: ...5 133 5 2 150 5 9 233 9 2 308 12 1 Depth C 168 6 6 168 6 6 168 6 6 245 9 6 245 9 6 241 9 5 323 12 7 Depth C with option B 173 6 8 173 6 8 173 6 8 250 9 8 250 9 8 D 180 7 1 240 9 4 240 9 4 270 10 6 36...

Страница 8: ...nits 4 Removable fan assembly 13 Pluggable RS485 terminal 5 Grounding clamp accessory 14 Fixed I O terminals 6 Shielded cable grounding clamp and strain relief accessory 15 Fixed I O terminals 7 Motor...

Страница 9: ...s MCB 102 MCB 103 accessories 14 Removable plugger for load sharing terminal 6 I O terminals 15 Shielded cable grounding clamps 7 I O terminals 16 Mains terminals 8 Pluggable RS485 terminals 17 Decoup...

Страница 10: ...DC supply or load sharing the motor may start at any time Unintended start during programming service or repair work can result in death serious injury or property damage Start the motor with an exter...

Страница 11: ...ectrical work conforms to national and local electrical codes Follow the procedures in this manual NOTICE HIGH ALTITUDES For installation at altitudes above 2000 m 6562 ft contact Danfoss regarding PE...

Страница 12: ...1 1 kW 1 5 hp 11 K 11 kW 15 hp 11 12 Voltage class T4 380 480 V 3 phases 13 15 IP class E20 IP20 16 17 RFI H2 C3 Class 18 Brake chopper X No B Built in3 19 LCP X No 20 PCB coating C 3C3 21 Mains termi...

Страница 13: ...maximum current from the frequency converter Correct rating of external fuses and circuit breakers Cooling and mounting Provide top and bottom clearance for air cooling see Table 3 2 for clearance re...

Страница 14: ...ion 130BF793 10 G Illustration 3 4 Normal Mounting 130BF794 10 G Illustration 3 5 Correct Horizontal Mounting Left Side Downwards 130BF795 10 G Illustration 3 6 Incorrect Horizontal Mounting Right Sid...

Страница 15: ...conductor and hence result in death or serious injury When a residual current operated protective device RCD is used for protection against electrical shock only an RCD of Type B is allowed on the su...

Страница 16: ...wire to reduce electrical noise Follow motor manufacturer wiring requirements 130BC500 10 FC 1 FC 1 FC 2 FC 2 FC 3 FC 3 PE PE Illustration 4 1 Grounding Principle Electrical Installation VLT Automati...

Страница 17: ...0 V PNP 27 D IN OUT 24 V 0 V 0 V PNP 24 V NPN 0 V 24 V 29 D IN OUT 24 V NPN 0 V PNP 0 V PNP 24 V NPN 33 D IN 32 D IN 95 P 5 00 2 1 ON UDC 89 BR 81 5 24 V NPN 0 V PNP 0 10 V DC UDC 88 RFI 3 0 V 250 V...

Страница 18: ...ontrol cables motor cables and mains cables 13 Common ground busbar Follow local and national requirements for cabinet grounding 5 Mains supply 14 Brake resistor 6 Bare unpainted surface 15 Metal box...

Страница 19: ...ing delta or TT TN S mains with a grounded leg grounded delta set parameter 14 50 RFI Filter to OFF enclosure sizes J6 J7 or remove the RFI screw enclosure sizes J1 J5 When off the internal RFI filter...

Страница 20: ...meter 5 14 Ter minal 32 Digital Input 0 No operation Digital input 24 V encoder Terminal 33 can be used for pulse input 33 Parameter 5 15 Ter minal 33 Digital Input 16 Preset ref bit 0 27 Parameter 5...

Страница 21: ...rter functioning in a typical operational mode Using shielded control cables The preferred method in most cases is to secure control and serial communication cables with shielding clamps provided at b...

Страница 22: ...l Communication Connect RS485 serial communication wiring to terminals 68 and 69 Shielded serial communication cable is recommended See chapter 4 3 1 Grounding Requirements for proper grounding 61 68...

Страница 23: ...e input voltage is balanced within 3 If not correct the input voltage imbalance before proceeding Repeat this procedure after the voltage correction 2 Ensure that any optional equipment wiring matches...

Страница 24: ...edit set up If the same set up acts as both active and edit set up only that set up number is shown factory setting When active and edit set ups differ both numbers are shown in the display set up 12...

Страница 25: ...cy converter from the mains Disconnect the frequency converter from the mains and wait for the frequency converter to fully discharge See the discharge time in Table 2 1 5 4 2 The Right key Function o...

Страница 26: ...ed Motor nominal speed Motor current Motor cont rated torque Resistance Rs Motor poles inductance Ld Asynchronous motor Motor current Minimum reference Maximum reference Ramp 1 ramp up time Ramp 1 ram...

Страница 27: ...16 13 Frequency Parameter 16 14 Motor current Parameter 16 16 Torque Nm Parameter 16 30 DC Link Voltage 5 4 5 Main Menu on NLCP The Main Menu gives access to all parameters 1 To enter Main Menu press...

Страница 28: ...up Table 5 5 Changing Values in Continuous Parameters For enumerated parameters the interaction is similar but the parameter value is shown in brackets because of the LCP 21 digits limitation 4 large...

Страница 29: ...play menu keys C Navigation keys and indicator lights LEDs D Operation keys and reset 130BD598 10 Auto On Reset Hand On Off Status Quick Menu Main Menu Alarm Log B a c k C a n c e l Info OK Status 1 1...

Страница 30: ...and reset Operation keys are at the bottom of the LCP Key Function 18 Hand On Starts the frequency converter in hand on mode An external stop signal by control input or serial communication overrides...

Страница 31: ...n to return to normal operation 5 4 10 Restoring Default Settings with LCP NOTICE Risk of losing programming motor data localization and monitoring records by restoration of default settings To provid...

Страница 32: ...performance 5 5 2 PM Motor Set up in VVC Initial programming steps 1 Set parameter 1 10 Motor Construction to the following options to activate PM motor operation 1a 1 PM non salient SPM 1b 3 PM sali...

Страница 33: ...meter 1 46 Position Detection Gain for different motors If the frequency converter fails to start or an overcurrent alarm occurs when the frequency converter starts check if the rotor is blocked or no...

Страница 34: ...ct 5 Verify that the motor running direction matches the setting in parameter 1 06 Clockwise Direction 5a When parameter 1 06 Clockwise Direction is set to 0 Normal default clockwise a Verify that the...

Страница 35: ...5 10 PROFIBUS VLT AutomationDrive FC 360 frequency converters support PROFIBUS If PROFIBUS is needed Order a new frequency converter on which the control cassette with PROFIBUS is pre installed Order...

Страница 36: ...tion status for RS485 Not used for PROFIBUS Termination resistor switch When the switch is turned on the termination resistor is in effect PROFIBUS address selector Use the switches in the selector to...

Страница 37: ...In the package of each control cassette with PROFINET a decoupling kit is provided for better mechanical fixation Install the decoupling kit after the control casette is installed To install the deco...

Страница 38: ...130BE308 10 Illustration 5 16 Place Ethernet Cables between Clamps Commissioning VLT AutomationDrive FC 360 36 Danfoss A S 03 2017 All rights reserved MG06A702 5 5...

Страница 39: ...mperature must be kept at a desired level by sensor feedback 130BC430 11 24V 12 DI1 18 DI2 19 DI3 27 DI4 29 DI5 3 2 DI6 3 3 DI7 3 1 COM 20 10V 50 AI1 53 AI2 54 COM 55 AO1 4 5 AO2 4 2 1 2 3 4 5 6 R1 R2...

Страница 40: ...arameter 3 16 Reference 2 Source 0 No function 0 No function Parameter 4 12 Motor Speed Low Limit Hz 25 0 Hz 25 0 Hz Parameter 4 14 Motor Speed High Limit Hz 50 0 Hz 50 0 Hz Parameter 5 10 Terminal 18...

Страница 41: ...n Loop Application Machine tools texturizers Parameter 0 16 Application Selection is set to 4 Simple Speed Closed Loop Description For precise speed applications with 24 V encoder feedback 130BC433 13...

Страница 42: ...meter Option value Parameter 1 00 Configuration Mode 0 Speed Open Loop Parameter 3 00 Reference Range 0 Min Max Parameter 3 15 Reference 1 Source 0 No Function Parameter 4 14 Motor Speed High Limit Hz...

Страница 43: ...ent 80 Parameter 2 07 Parking Time 0 5 Parameter 2 10 Brake Function 0 Off Parameter 3 03 Maximum Reference 250 Hz Parameter 4 14 Motor Speed High Limit Hz 250 Hz Parameter 4 16 Torque Limit Motor Mod...

Страница 44: ...eter 4 18 Current Limit 160 Parameter 5 10 Terminal 18 Digital Input 8 Start Parameter 5 11 Terminal 19 Digital Input 0 No operation Parameter 5 12 Terminal 27 Digital Input 2 Coast inverse Parameter...

Страница 45: ...al 53 mode 1 Voltage Default value Notes comments Table 6 9 Analog Speed Reference Voltage Parameters 130BF819 10 24 V D IN D IN D IN D IN D IN D IN 10 V A IN A IN COM A OUT 12 31 18 19 27 29 32 33 50...

Страница 46: ...d Down 6 2 4 Start Stop Parameters 130BF822 10 FC 24 V D IN D IN D IN D IN D IN D IN 10 V A IN A IN COM A OUT 12 19 18 27 29 32 33 50 53 54 55 42 31 D IN Function Setting Parameter 5 10 Ter minal 18 D...

Страница 47: ...double insulation on the thermistors Parameters 130BF824 10 24 V D IN D IN D IN D IN D IN 10 V A IN A IN COM A OUT 12 31 18 19 27 29 32 33 50 53 54 55 42 FC D IN D IN Function Setting Parameter 1 90 M...

Страница 48: ...operation to prevent damage to the frequency converter and other equipment When a trip lock occurs the motor coasts to a stop The frequency converter logic continues to operate and monitor the frequen...

Страница 49: ...the motor terminals 14 Earth fault X X Discharge from output phases to ground 16 Short circuit X X Short circuit in motor or on motor terminals For J7 units if this alarm occurs on power up check whe...

Страница 50: ...utout temperature of the control card is 80 C 176 F 69 Power card temp X X X 70 Illegal FC config X X 80 Frequency converter initialized to default value X All parameter settings are initialized to de...

Страница 51: ...000002 00 512 Inverter overld Reserved Reserved Inverter overld Reserved Output freq high Quick stop 10 000004 00 1024 DC undervolt Start failed Reserved DC undervolt Reserved Output freq low DC brake...

Страница 52: ...ved Reserved 26 040000 00 67108864 Brake resistor Reserved Reserved Reserved Reserved Reserved External interlock 27 080000 00 13421772 8 Brake IGBT Reserved Reserved Reserved Reserved Reserved Reserv...

Страница 53: ...nged while the frequency converter is running Err The password that is input via the LCP is incorrect Table 7 3 Error Code List 7 5 Troubleshooting Symptom Possible cause Test Solution Motor not runni...

Страница 54: ...with reduced load Review the specifications for the application Loose connections Perform pre start up check for loose connections Tighten loose connections Mains current imbalance greater than 3 Prob...

Страница 55: ...ntinuous kVA 480 V AC kVA 0 9 1 3 1 7 2 5 2 8 4 0 5 2 6 8 9 1 11 6 Maximum input current Continuous 3x380 440 V A 1 2 1 6 2 1 2 6 3 5 4 7 6 3 8 3 11 2 15 1 Continuous 3x441 480 V A 1 0 1 2 1 8 2 0 2 9...

Страница 56: ...um input current Continuous 3x380 440 V A 22 1 29 9 35 2 41 5 57 70 3 84 2 102 9 140 3 Continuous 3x441 480 V A 18 4 24 7 29 3 34 6 49 3 60 8 72 7 88 8 121 1 Intermittent 60 s overload A 33 2 44 9 52...

Страница 57: ...8 0 98 2 Table 8 3 Mains Supply 3x380 480 V AC Normal Duty1 1 Heavy duty 150 160 current during 60 s Normal duty 110 current during 60 s 2 The typical power loss is at nominal load conditions and expe...

Страница 58: ...aximum 160 for 60 s1 Overload torque high overload Maximum 160 for 60 s1 Starting torque normal overload Maximum 110 for 60 s1 Overload torque normal overload Maximum 110 for 60 s Starting current Max...

Страница 59: ...push pull driven Maximum frequency at terminal 29 33 5 kHz open collector Minimum frequency at terminal 29 33 4 Hz Voltage level See the section on digital input Maximum voltage on input 28 V DC Input...

Страница 60: ...load cos 0 4 250 V AC 0 2 A Maximum terminal load DC 1 1 on 01 02 04 05 NO Resistive load 30 V DC 2 A Maximum terminal load DC 13 1 on 01 02 04 05 NO Inductive load 24 V DC 0 1 A Maximum terminal load...

Страница 61: ...EN 61800 3 EN 61000 6 1 2 EN 61000 4 2 EN 61000 4 3 EN 61000 4 4 EN 61000 4 5 EN 61000 4 6 Energy efficiency class1 IE2 1 Determined according to EN 50598 2 at Rated load 90 rated frequency Switching...

Страница 62: ...cy converter and other equipment Select fuses according to recommendations Possible damages can be limited to be inside the frequency converter NOTICE Using fuses or circuit breakers is mandatory to e...

Страница 63: ...4 4 J2 3 0 5 5 4 7 5 0 8 7 1 0 8 7 1 0 8 7 1 0 8 7 1 3 26 6 0 44 3 89 0 5 4 4 J3 7 5 10 0 8 7 1 0 8 7 1 0 8 7 1 0 8 7 1 3 26 6 0 44 3 89 0 5 4 4 J4 11 15 15 20 1 2 10 6 1 2 10 6 1 2 10 6 1 2 10 6 1 6...

Страница 64: ...converter IP Ingress protection LCP Local control panel MCT Motion control tool NLCP Numerical local control panel ns Synchronous motor speed PM N Nominal motor power PELV Protective extra low voltage...

Страница 65: ...PCD 8 Write For Application 3409 PCD 9 Write For Application 3410 PCD 10 Write For Application 3421 PCD 1 Read For Application 3422 PCD 2 Read For Application 3423 PCD 3 Read For Application 3424 PCD...

Страница 66: ...ded Detection 1 93 Thermistor Source 0 None 1 Analog Input 53 2 Analog Input 54 3 Digital input 18 4 Digital input 19 5 Digital input 32 6 Digital input 33 7 Digital input 31 2 Brakes 2 0 DC Brake 2 0...

Страница 67: ...c Hold 184 Sync Latch Preset Factor Index 185 Sync Preset Factor Idx0 186 Sync Preset Factor Idx1 5 11 Terminal 19 Digital Input Same choices with 5 10 10 Reversing 5 12 Terminal 27 Digital Input Same...

Страница 68: ...minal 54 Low Ref Feedb Value 4999 4999 0 6 25 Terminal 54 High Ref Feedb Value 4999 4999 Size related 6 26 Terminal 54 Filter Time Constant 0 01 10 s 0 01 s 6 29 Terminal 54 mode 0 Current mode 1 Volt...

Страница 69: ...og Input 53 2 Analog Input 54 7 Frequency input 29 8 Frequency input 33 11 Local bus reference 32 Bus PCD 7 46 Process PID Feed Fwd Normal Inv Ctrl 0 Normal 1 Inverse 7 48 PCD Feed Forward 0 65535 0 7...

Страница 70: ...67 Pulse input 29 Hz 1668 Pulse input 33 Hz 1669 Pulse output 27 Hz 1670 Pulse output 29 Hz 1671 Relay output 1672 Counter A 1673 Counter B 1679 Analog output 45 mA 1684 Comm Option STW 1685 FC Port C...

Страница 71: ...nly 1 Broadcast Multicast 12 96 Port Config 0 Normal 1 Mirror Port 1 to 2 2 Mirror Port 2 to 1 10 Port 1 disabled 11 Port 2 disabled 254 Mirror Int Port to 1 255 Mirror Int Port to 2 12 98 Interface C...

Страница 72: ...2 Initialisation 14 24 Trip Delay at Current Limit 0 60 s 60 s 14 25 Trip Delay at Torque Limit 0 60 s 60 s 14 27 Action At Inverter Fault 0 Trip 1 Warning 14 29 Service Code 0 0x7FFFFFFF 0 14 3 Curre...

Страница 73: ...Hz 18 82 Center Winder Output 5000 5000 Hz 0 Hz 18 83 Line Speed 5000 5000 Hz 0 Hz 18 84 Diameter 0 100 0 18 85 Tapered Tension Set Point 0 100 0 18 86 Tension Feedback 0 100 0 18 9 PID Readouts 18 9...

Страница 74: ...1073741824 1073741824 0 37 03 Pos Type 0 Absolute 1 Relative 37 04 Pos Velocity 1 30000 RPM 100 RPM 37 05 Pos Ramp Up Time 50 100000 ms 5000 ms 37 06 Pos Ramp Down Time 50 100000 ms 5000 ms 37 07 Pos...

Страница 75: ...switch 21 E Electrical noise 14 EMC 59 EMC compliant installation 13 Encoder rotation 32 Energy efficiency 53 54 55 Energy efficiency class 59 External command 4 External controller 3 F Fault log 27...

Страница 76: ...l 8 Quick menu 23 27 R Reference 27 Relay output 58 Remote command 3 Reset 27 28 30 46 59 RFI filter 17 Run command 33 S Safety 9 Serial communication 3 19 20 28 46 Set up 33 Shielded cable 13 Shielde...

Страница 77: ...Index Quick Guide MG06A702 Danfoss A S 03 2017 All rights reserved 75...

Страница 78: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Отзывы: