PE
FC
PE
FC
130BB924.12
PE
PE
69
69
68
68
1
2
<10 mm
1
Minimum 16 mm
2
(6 AWG)
2
Equalizing cable
Illustration 4.11 Twisted-pair Cables without Terminal 61
4.7 Jumper Terminals 12 and 27
When the factory default programming values are used,
connect a jumper wire between terminal 12 and terminal
27 for the frequency converter to operate.
•
Digital input terminal 27 is designed to receive a
24 V DC coast command. In many applications,
wire a coast device to terminal 27.
•
When no interlock device is used, wire a jumper
between control terminal 12 and terminal 27. This
provides internal 24 V signal on terminal 27.
•
No signal present prevents the unit from
operating.
•
Only for GLCP: When the status line at the
bottom of the LCP reads
AUTO REMOTE COAST
, it
indicates that the unit is ready to operate but is
missing an input signal on terminal 27.
4.8 Serial Communication
Connect RS485 serial communication wiring to terminals
(+) 68 and (-) 69.
•
Shielded serial communication cable is
recommended.
•
See
chapter 4.3.1 Grounding Requirements
for
proper grounding.
61
68
69
+
130BB489.10
RS485
Illustration 4.12 Serial Communication Wiring Diagram
For basic serial communication set-up, select the following:
1.
Protocol type in
parameter 8-30 Protocol
.
2.
Frequency converter address in
parameter 8-31 Address
.
3.
Baud rate in
parameter 8-32 Baud Rate
.
Two communication protocols are internal to the
frequency converter.
•
Danfoss FC
•
Modbus RTU
Follow motor manufacturer wiring requirements.
Functions can be programmed remotely using the protocol
software and RS485 connection, or in
parameter group 8-**
Communications and Options
.
Selecting a specific communication protocol changes
various default parameter settings to match the specifi-
cations of the protocol and makes extra protocol-specific
parameters available.
Electrical Installation
VLT
®
AutomationDrive FC 360
20
Danfoss A/S © 03/2017 All rights reserved.
MG06A702
4
4