VLT
®
AutomationDrive FC 302
N450
N500
High/normal overload
HO
NO
HO
NO
(High overload=150% current during 60 s, normal overload=110%
current during 60 s)
Typical shaft output at 400 V [kW]
450
500
500
560
Typical shaft output at 460 V [hp]
600
650
650
750
Typical shaft output at 500 V [kW]
530
560
560
630
Enclosure size
E2h/E4h
E2h/E4h
Output current (3-phase)
Continuous (at 400 V) [A]
800
880
880
990
Intermittent (60 s overload) (at 400 V) [A]
1200
968
1320
1089
Continuous (at 460/500 V) [A]
730
780
780
890
Intermittent (60 s overload) (at 460/500 V) [A]
1095
858
1170
979
Continuous kVA (at 400 V) [kVA]
554
610
610
686
Continuous kVA (at 460 V) [kVA]
582
621
621
709
Continuous kVA (at 500 V) [kVA]
632
675
675
771
Maximum input current
Continuous (at 400 V) [A]
771
848
848
954
Continuous (at 460/500 V) [A]
704
752
752
858
Maximum number and size of cables per phase (E2h)
- Mains and motor without brake [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Mains and motor with brake [mm
2
(AWG)]
5x240 (5x500 mcm)
5x240 (5x500 mcm)
- Brake or regen [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Maximum number and size of cables per phase (E4h)
- Mains and motor [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Brake [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
- Load share or regen [mm
2
(AWG)]
4x185 (4x350 mcm)
4x185 (4x350 mcm)
Maximum external mains fuses [A]
1)
1200
1200
Estimated power loss at 400 V [W]
2), 3)
8352
9473
9449
11102
Estimated power loss at 460 V [W]
2), 3)
7182
7809
7771
9236
Efficiency
3)
0.98
0.98
Output frequency [Hz]
0–590
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
100 (212)
Control card overtemperature trip [
°
C (
°
F)]
80 (176)
80 (176)
Power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
Fan power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
Active in-rush card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
Table 7.4 Electrical Data for Enclosures E2h/E4h, Mains Supply 3x380–500 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
Specifications
Design Guide
MG38C202
Danfoss A/S © 01/2018 All rights reserved.
39
7
7
Содержание VLT AutomationDrive FC 302
Страница 2: ......
Страница 211: ...Index Design Guide MG38C202 Danfoss A S 01 2018 All rights reserved 209...