4 Troubleshooting

4.1  Warnings and Alarms

NOTICE

Refer to the relevant 

operating instructions

 for an

overview of warning and alarm types and for the full list
of warnings and alarms.

Alarm word, warning word, and CANopen warning word
are shown on the frequency converter display in hex
format. When there is more than 1 warning or alarm, the
sum of all warnings or alarms is shown. Alarm word,
warning word, and CANopen warning word can also be
displayed using the serial bus in:

Parameter 16-90 Alarm Word

.

Parameter 16-91 Alarm Word 2

.

Parameter 16-92 Warning Word

.

Parameter 16-93 Warning Word 2

.

4.2  Troubleshooting

4.2.1 LED Status

The 2 bi-colour LEDs on the CANopen card indicate the
status of CANopen communication:

The lower LED (NS) indicates the net status.

The upper LED (MS) indicates the module status.

Illustration 4.1 LED Panel VLT

®

 CANopen MCA 105

State

Red LED

Description

No error

Off

No error.

Warning limit
reached

Single flash CAN error counter has reached/

exceeded warning level.

Error control
event

Double flash Node guard event has occurred.

Sync error

Triple flash

Sync message has not been
received within the configured
timeout (object 0x1006).

Bus off

On

Device in bus off-state.

Table 4.1 LED: Module Status (MS)

State

Red LED

Description

Stopped

Single flash Device in stopped state.

Pre-operational Triple flash

Device in pre-operational state.

Operational

On

Device in operational state.

Table 4.2 LED: Network Status (NS)

4.2.2 No Communication with the

Frequency Converter

When there is no communication with the frequency
converter, proceed with the following checks:

1.

Check that cabling is correct.
Check that the cables are connected to the
correct terminals as shown in 

Illustration 3.6

.

2.

Check that the bus connection is terminated at
both ends.
If not, terminate the bus connection with
termination resistors at the initial and final nodes.

3.

Check that each node connected to the CANopen
network has a unique node ID (address). If 2
devices have the same node ID, it leads to
malfunction in the network.

4.

Communication drops out after some time. Check
the installation for correct routing of the
CANopen cables. Check if the screen of the motor
cable is mounted correctly.

5.

Communication is unstable. Check

parameter 10-05 Readout Transmit Error Counter

and 

parameter 10-06 Readout Receive Error

Counter

. These 2 parameters have to be close to 0

most of the time. If they show higher values,
check the CANopen cable for interference, wrong
termination, and so on.

Troubleshooting

Installation Guide

MG33J402

Danfoss A/S © 05/2015 All rights reserved.

11

4

4

Содержание VLT AutomationDrive FC 301

Страница 1: ...MAKING MODERN LIVING POSSIBLE Installation Guide VLT CANopen MCA 105 VLT AutomationDrive FC 301 302 vlt drives danfoss com...

Страница 2: ......

Страница 3: ...ion 6 3 1 Safety Instructions 6 3 2 EMC compliant Installation 6 3 3 Grounding 6 3 4 Cable Routing 6 3 5 Mounting 7 3 6 Setting Address Switches 8 3 7 Electrical Installation 8 3 8 Reassembling Cover...

Страница 4: ...ng Guide provides information about configuring the system controlling the frequency converter parameter access programming troubleshooting as well as some typical application examples Supplementary p...

Страница 5: ...nificant bit NMT Network management N A Not applicable OD Object directory PCD Process data PDO Process data object PLC Programmable logic controller PNU Parameter number RPDO Receive process data obj...

Страница 6: ...sharing the motor may start at any time Unintended start during programming service or repair work can result in death serious injury or property damage The motor can start with an external switch a...

Страница 7: ...ectrical work conforms to national and local electrical codes Follow the procedures in this manual CAUTION INTERNAL FAILURE HAZARD An internal failure in the frequency converter can result in serious...

Страница 8: ...ns as short as possible Establish electrical contact between the cable screen and the frequency converter enclosure by using metal cable glands or by using the clamps provided on the equipment Use hig...

Страница 9: ...on 3 3 or with the connector facing down for bottom cable entry see Illustration 3 4 If an MCB option is installed only top cable entry is possible 5 Remove the knock out plate from the new LCP cradle...

Страница 10: ...Resistance m m Cable cross section mm2 Termination resistor 500 100 60 0 34 0 6 120 250 250 40 0 5 0 6 125 500 50 1000 26 0 75 0 8 20 2500 10 5000 Table 3 3 Cable Specifications 3 7 2 Wiring Procedure...

Страница 11: ...cable through cable glands 2 Mount the fieldbus connector on the fieldbus option CAN_L Drain CAN_H 3 Prepare the fieldbus cable by stripping a section of the cable insulation Keep the unshielded wire...

Страница 12: ...ide the unit see Illustration 3 9 130BC527 10 Illustration 3 9 Wiring for Enclosure Sizes D E and F 3 8 Reassembling Cover 1 Mount the new front cover and the LCP 2 Attach the sticker with the correct...

Страница 13: ...off state Table 4 1 LED Module Status MS State Red LED Description Stopped Single flash Device in stopped state Pre operational Triple flash Device in pre operational state Operational On Device in op...

Страница 14: ...6 EMC interference 6 EMC compliant installation 6 Exploded view 7 G Grounding 6 H High voltage 4 I Intended use 2 Items supplied 2 L Leakage current 4 LED panel 11 LED status 11 Load sharing 4 M Moto...

Страница 15: ...Index Installation Guide MG33J402 Danfoss A S 05 2015 All rights reserved 13...

Страница 16: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Отзывы: