Pin no.
Terminal
Colour
Name
1
–
–
Not used
2
CAN_L
Blue
CAN LOW
3
Drain
(bare)
Screen
4
CAN_H
White
CAN HIGH
5
–
–
Not used
Illustration 3.6 Fieldbus Cable Terminal Connections
CANopen termination
Install the termination resistors at each end of the bus line.
Mount the resistor between terminal 2 (CAN_L) and
terminal 4 (CAN_H).
The resistors have the following specification:
•
121
Ω
•
1% Metal film
•
1/4 W
Illustration 3.7 Termination Resistor Mounted
Wiring procedure for enclosure sizes A4–A5, B1–B4, and
C1–C4
1.
Push the cable through cable glands.
2.
Mount the fieldbus connector on the fieldbus
option ( CAN_L, Drain, CAN_H).
3.
Prepare the fieldbus cable by stripping a section
of the cable insulation. Keep the unshielded wire
as short as possible. For cable specifications, refer
to
chapter 3.7.1 Cable Specifications
.
4.
Connect the fieldbus cable wires to the terminals
according to the colour code of the wires, see
Illustration 3.6
.
5.
Fix the cable screen to the metal base plate using
cable clamp or cable tie, see
Illustration 3.8
.
6.
Tighten cable glands securely.
130BD864.10
Illustration 3.8 Wiring for Enclosure Sizes A4–A5, B1–B4, and
C1–C4
Installation
Installation Guide
MG33J402
Danfoss A/S © 05/2015 All rights reserved.
9
3
3